Technical specifications (cont.) – MovinCool CM12 User Manual
Page 22

22
TECHNICAL SPECIFICATIONS (cont.)
• Specifications are subject to change without notice.
Note:
*1: With two 6-foot (1.8 m) ducts containing one 90° bend each, supply grill and
return grill with filter [0.16 IWG (40 Pa) external static pressure] on high fan
speed.
*2: When ambient temperature is lower than 65 °F (18 °C), operation may be
interrupted due to anti-freeze protection activation.
*3: Confirm pressure drop of duct, grills, and filter with manufacture’s
specifications.
*4: Measured at 3 feet (1.0 m) under the ceiling with evaporator duct and ceiling
tile.
ITEM
SPECIFICATIONS
Condensate Pump
Capacity
Pump Rate
5.0 gal/h (19 L/h)
Max. Head
4 ft (1.2 m)
Operating Condition
Range
*2
Evaporator Air
Inlet
Max.
95 °F (35 °C), 50 %RH
Min.
65 °F (18 °C), 50 %RH
Condenser Air
Inlet
Max.
113 °F (45 °C), 50 %RH
Min.
65 °F (18 °C), 50 %RH
Maximum Duct Length
*3
Cold Duct
20 ft (6.1 m)
Hot Duct
10 ft (3.0 m)
Maximum Sound Level
*4
High
52 dB (A)
Low
52 dB (A)