HT34-PV Series Power Vent Gas Fireplace

Part No. XG0530 - 041510

Appendix A - Termination Locations

A = clearance to the termination frame above grade, veranda, porch, deck,

or balcony [16 inches (41 cm) minimum]

B = clearance to door, or sides and top of window, that may be opened [16

inches (41 cm) minimum for appliances 100 000 BTU/H (30kW)]

C = clearance to bottom of window that may be opened horizontally [36 inches

(92 cm) minimum for appliances 100 000 BTU/H (30kW)]

D = no clearance to permanently closed window when installed with approved

glass penetration termination

E = clearance to permanently closed window [16 inches 41 cm recommended

to prevent condensation on window]

F = vertical clearance to ventilated soffit located above the termination within a

horizontal distance of 2 feet (61 cm) from the centreline of the termination

[22 inches (56 cm) minimum]

G = c l e a r a n c e t o u n v e n t i l a t e d s o f f i t [ 1 6 i n c h e s

( 4 1 c m ) m i n i m u m t o n o n - c o m b u s t i b l e s ]

[22 inches (56 cm) minimum to combustibles]

H = clearance to outside corner [9 inches (23 cm) minimum]
I = clearance to inside corner [12 inches (31 cm) minimum]
J = * not to be installed above a meter/regulator assembly within

40" (103 cm) horizontally from the centreline of the regulator

K = clearance to service regulator vent outlet [3 feet minimum in the United

States] [*6 feet (1.8 m) minimum in Canada]

L = clearance to non-mechanical air supply inlet to building or the combustion

air inlet to any other appliance [16 inches (41 cm) minimum for appliances

100 000 BTU/H (30kW)]

M = clearance to mechanical air supply inlet [*6 feet (1.8 m) minimum]

N =

clearance above paved sidewalk or a paved driveway located on public

property [*7 feet (2.1 m) minimum]

P = clearance under veranda, porch, deck, or balcony

[16 inches (41 cm) minimum

to non-combustibles]

[22 inches (56 cm) minimum

to combustibles]

Q = clearance above a roof [24 inches (61 cm) minimum]
R = clearance to adjacent walls and neighboring buildings

[18 inches (46 cm) minimum]

S = c l e a r a n c e f r o m c o r n e r i n r e c e s s e d l o c a t i o n

[12 inches (31 cm) minimum]

T = m a x i m u m d e p t h i n r e c e s s e d l o c a t i o n

[48 inches (122 cm) minimum]

U = minimum width for back wall of recessed location

[24 inches (61 cm) minimum]

V = no horizontal clearance between the frames of two terminations that

are level.

W = horizontal clearance between the frames of two terminations that are

not level. [36 inches (92 cm) minimum]

a vent shall not terminate directly above a sidewalk or paved driveway

which is located between two single family dwellings and serves both

dwellings

only permitted if veranda, porch, deck, or balcony has an open side that

is equal to or greater than the depth of the enclosed area

* as specified in CGA B149 Installation Codes. Note: local Codes or

Regulations may require different clearance.