Section 3-2-1: venting layout, Section 3-2, Installing a roof mounted direct vent termination – Montigo H42DF ST User Manual
Page 11: Pvtk-1), Installation
H*42DF ST Indoor Gas Fireplace
Page 11
XG0237 - 150204.1
Installation
Section 3-2:
Installing a Roof Mounted Direct Vent Termination
(PVTK-1)
This section applies to installations where the direct vent termi-
nation will be roof mounted.
Section 3-2-1: Venting Layout
Selection of components and details of venting lay out should
adhere to the following guidelines:
The maximum termination point is 32’ above the fireplace (NOTE:
if the maximum termination height is used, the flame pattern
may be affected).
The Vertical termination must be a minimum 2’ higher than where
the termination exits the roofing materials, (asphalt shingles,
cedar shakes, etc). This distance should be measured from the
high side of the roof slope where the flue flashing intersects the
roofing materials. (see Figures 8 to 8c).
Termination location must be a minimum 6’ from a mechanical
air inlet.
Termination location must be a minimum 18” from a parapet wall.
For a more detailed diagram of allowed termination locations,
see Appendix A.
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made for vertical vent runs.
Firestops must be installed as required by National & local codes.
Ensure all horizontal runs are supported with a minimum of 3
supports per 10’ of venting.
Install all roof flashing and storm collars as shown.
Figure 8. Top vent, Roof mounted termination with no offset in vent run.
Figure 8a. Top vent, Roof mounted with 1 offset (1 offset= two 90° bends).
Figure 8b. Top vent, Roof mounted with 2 offsets (1 offset= two 90° bends).
Roof mounted Terminations
The following details are some possible configurations for Roof
mounted terminations. See below.
PVTK1 Termination
PVTK1 Termination
PEXT
PXT-10
Adaptor
Flue
Collar
PVTK1 Termination