F. service – Greenheck Network Interface Controller for Tempered Air Products (476811) User Manual
Page 9

9
Network Interface Controller for Tempered Air Products
T
HIS
SCREEN
ALLOWS
THE
USER
TO
ADJUST
BAC
NET
IP
PARAMETERS
.
This screen only appears if the selected BMS protocol is set to BACnet IP/Eth and
BACnet Plugin = YES.
If a BACnet IP card has been installed, the default parameters can be changed
via the controller display. The card is in DHCP mode from the factory. Once
communication is established, the user can enter static IP parameters.
To view current parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view BACnet Read/Write screen.
3. Change Function to Read and Update? to YES.
Current BACnet IP parameters should now be displayed in the BACnet TCP/IP
SETUP screen. If all values appear to be zeros, consult the factory. (Make sure
you have allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the Function to READ.
To change BACnet TCP/IP parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to BMS Config menu and view TCP/IP SETUP screen.
3. Move cursor to desired parameter by pressing the
buttons. Press
to select the parameter to change. Press the
buttons to adjust
the parameter. Press
to save adjusted value.
4. Once desired parameters have been entered, go to BACnet Read/Write
screen. Change Function to Write and Update? to YES.
5. Reboot the controller by cycling power to the unit. Allow several minutes
for the controller to initialize.
6. View TCP/IP parameters. If changed values did not save, contact the
factory.
TCP/IP SETUP
Instance: 77000
IP set by:
DHCP
IP: 128.2.104.134
Subnet: 255.255.000.000
Gatewy: 128.2.0.12
TCP/IP SETUP
DNS 1:
193.168.001.001
DNS 2:
193.168.001.001
Type: IP
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to confirm
write command.
F.
Service
d. Service Settings
a. Working hour set
b. Probe adjustment
c. Password/Defaults
The Service Settings menu allows the user to change the default Service
Password (1000), save and restore default parameters, and adjust probe
values.
T
HIS
SCREEN
ALLOWS
THE
USER
TO
VIEW
UNIT
RUN
HOURS
,
AND
ALTER
SET
POINTS
FOR
MAINTENANCE
.
Run hours: The amount of time in hours that the unit has been powered.
Set Point: The amount of running time in hours before a maintenance alarm
should occur.
Reset to Zero: Reset the measured amount of run time.
T
HE
P
ROBE
A
DJUSTMENT
MENU
ALLOWS
THE
USER
TO
CALIBRATE
SENSOR
PROBES
WITH
AN
OFFSET
VALUE
.
Similar screens are available for remaining sensor probes.
T
HIS
SCREEN
ALLOWS
THE
USER
TO
CHANGE
THE
S
ERVICE
L
EVEL
PASSWORD
(PW1)
MAINTENANCE HOURS
SYSTEM
Run hours:
0000h
Set Point:
0000h
Reset to Zero?
No
Analog Input
Outside Temperature
Input B3
Offset: 0.0°F
Value: 70.5°F
User Default
Insert new service password
(PW1): 1000
®