beautypg.com

G. service – Greenheck Network Interface Controller for Tempered Air Products (476811) User Manual

Page 16

background image

16

Network Interface Controller for Tempered Air Products

To view the current
parameters, go the BMS
Config menu within the
controller by pressing
the

Prg

or

key.

To access the BMS
Config sub-menu, enter
the service-password
(Default=1000).

Protocol must be
BACnet MSTP and
BACnet Plugin must be
YES.

Press the

button

arrow to view next
screen.

Current BACnet MSTP
parameters should be
displayed. If values
appear to be zero, follow
the procedure below.

To read current settings:
1. Power on controller

and allow several
minutes to initialize.

2. Go to BMS Config menu and view BACnet Read/

Write screen.

3. Change Function to Read and Update? to YES.

Current BACnet MSTP parameters should now be
displayed in the BACnet MSTP SETUP screen. If
all values appear to be zeros, consult the factory.
(Make sure you have allowed several minutes for the
controller to initialize). *Values may appear to be zero
prior to setting the Function to READ.

To change BACnet MSTP parameters:

1. Power on the controller and allow several minutes

to initialize.

2. Go to BMS Config menu and view MSTP SETUP

screen.

3. Move cursor to desired parameter by pressing the

buttons. Press

to select the parameter

to change. Press the

buttons to adjust the

parameter. Press

to save adjusted value.

Parameter

Factory

Minimum

Maximum

Device Instance

77000

0

4194303

Station Address

0

0

127

Max Master

127

0

127

Max Info Frames

20

0

255

Baudrate

38400

9600-19200-38400-76800

4. Once desired parameters have been entered, go

to BACnet Read/Write screen. Change Function to
Write
and Update? to YES.

5. Reboot the controller by cycling power to the unit.

Allow several minutes for the controller to initialize.

6. View MSTP parameters. If changed values did not

save, contact the factory.

The communication card
is located in the Serial
Card port on the face of
the controller. The card
includes two sets of LED
lights for communication
troubleshooting.

Status LED: Indicates the status of communication
between the card and controller.

• Quick green-off-green if communication with

controller is ok.

• Slow red-off-red if communication is not

established.

RS485 LED: Indicates the status of communication
with the BACnet MSTP network. Wait for 40 seconds
to determine status of communication.
• Green with occasional red, communication is OK.
• Green and red both on, communications is not

established.

Communication Troubleshooting

See Carel Data sheet for more info.

If attempting to communicate with the controller over
BACnet MSTP, refer to the card LEDs for system
information.

Status LED slow red blink
• Confirm card is firmly plugged in.
• Confirm BMS Protocol is set to BACnet MSTP.

RS485 LED green and red both on
• Confirm system and card baudrate are the same.
• Confirm card Max Master is equal to or greater

than the Station (MAC) Address of the Master with
the highest address.

Recalling Factory Parameters

Follow this procedure to revert to factory parameters
for one power cycle. When restarted, the card will
resume using the previous user parameters.

1. With controller off, hold the push button located

on the BACnet MSTP card, while powering the
controller back on.

2. Continue to hold the button, while watching the

Status LEDs. Wait for the Status LEDs to blink red
slowly, and release before the third slow flash.

3. Wait for about one minute for the factory

parameters to be loaded.

The card is loaded with the following default BACnet
MSTP parameters.

BACnet® MSTP Quick Start

BMS Configuration

Protocol: BACnet

MSTP

BACnet Plugin?

YES

MSTP SETUP

Instance: 77000

Baudrate 38400
MAC Addr:

0

MaxMasters: 127
MaxInfoFrames: 20

BACnet Read/Write

Function: Read

Update? Yes

*Cycle unit power to confirm
write command.

G.

Service

c. BMS Config

Push Button

Status LED

RS485 LED

®