Typical wiring diagram – Greenheck Network Interface Controller for Tempered Air Products (476811) User Manual
Page 14

14
Network Interface Controller for Tempered Air Products
CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
LEGEND
GEXXXXD000XX101BL01
WIRE COLOR CODE
Wiring Diagram Code:
BK BLACK
BL
BLUE
BR BROWN
GY GRAY
LT BL
LIGHT BLUE
O
ORANGE
PK PINK
PR
PURPLE
R
RED
W
WHITE
Y
YELLOW
Wiring Template: L01
GND
Y4
GND
ID2
J13
B5
B6
ID1
B2
B3
B4
J2
B1
GND
CONTROLLER
pCO5 INTERFACE
J12
NO4
NO3
J1
C3
BLUE
G
GO
J3
NO6
NO5
C5
GND
Y1
Y2
J9
Y3
OAI
OAD
NO2
C2
J11
NC1
NO1
C1
(PWM)
J10
DDC Code: Verison - BMS v 1.10
TO TERMINAL "R"
TO TERMINAL "C"
R
C
(0/10V)
(0/10V)
(0/10V)
UNIT ELECTRICAL BOARD TERMINALS/COMPONENTS
NETWORK INTERFACE CONTROLLER/COMPONENTS
NETWORK INTERFACE CONTROLLER TO UNIT CONNECTION WIRING DIAGRAM
WHITE
24 VAC
OAD
OUTDOOR AIR DISCHARGE TEMP SENSOR
OAI
OUTDOOR AIR INLET TEMP SENSOR
POINTS LIST
Analog
1
Outside_Air_Temp
Analog
2
Supply_Air_Temp
Digital
10
Unit_Start_Stop
Digital
11
Reset_Alarms
Digital
16
Heat_Stg1_Command
Digital
20
Global_Alarm
Digital
23
Fan_Proving_Status
Digital
25
Dirty_Filter_Status
Digital
27
Supply_Air_Low_Limit
Digital
30
Sensor_B3_Out_Of_Range
Digital
31
Sensor_B4_Out_Of_Range
FOR MANUAL GO TO WWW.GREENHECK.COM
AND SEARCH "476811".
G
®
PINK
TO TERMINAL "G"
G
1
REPLACES S1 FAN SWITCH
FACTORY WIRED
UNIT START/STOP
X X X X
0 0 0 X X
0
b
TYPE
ADDRESS
NAME
TO "C" ON PS2
TO "NO" ON PS2
NO
PS2
C
D
REPLACES FIELD INTERFACE
CONNECTION TO PS2
DIRTY FILTER STATUS
FACTORY WIRED
LT. BLUE
RED
TO TERMINAL "W1"
W1
1
REPLACES S4 CALL FOR HEAT SWITCH
FACTORY WIRED
HEATING STAGE 1
BROWN
TO ST1-AUX
ST1-AUX
TO ST1-AUX
FAN PROVING STATUS
PINK
YELLOW
NO
C
Typical Wiring Diagram
®