Network Interface Controller for Tempered Air Products

Display is hard to read.

Unit Controller Display: Hold

Esc

or

ESC and

ENTER at the same time,

while pressing

DOWN or

UP to adjust display contrast.

Remote Display: Hold

or

!

ALARM,

Prg

or

PRG, and

Esc

or

ESC at the

same time, while pressing

DOWN or

UP to adjust display contrast.

Remote display panel
displays “NO LINK” or
is blank.

Hold

DOWN,

UP and

ENTER for 4 seconds. Set the display address

to 32. The display requires a standard 24 AWG six conductor phone cable
connected to the unit controller.

Red alarm button is
flashing.

Press the

or

!

ALARM button to review and clear unit alarms. Enter the

DATA LOGGER menu to view previous alarms.

Controller resets itself
or is not on.

Check the supply voltage to the controller at terminals G-G0. The board requires
24VAC. Check the 24VAC transformer in the unit control center.

Menus are locked with
a password.

The factory default Manufacturer Password = 1000.
The factory default Service Password = 1000.

Temperature sensor
failure.

Check the analog input terminal block (labeled terminals B1, B2, B3, etc) for loose
wires. Disconnect temperature sensors to check sensor resistance.

Troubleshooting

NTC Temperature Sensor Chart