Remedy
If the status code is displayed all the time: notify a Fronius-
trained service engineer
486
-
External NO contact is open
-
Optional measuring and monitoring relay has tripped
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
Close external NO contact;
check measuring and monitoring relay
If this status code keeps recurring, contact your system engi-
neer
487
Air inlet temperature sensor is faulty
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
Replace air inlet temperature sensor - notify a Fronius-trained
service engineer
488
AC measurement device is faulty
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
notify a Fronius-trained service engineer
490, 491
Internal communication error
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
notify a Fronius-trained service engineer
492
DC main switch is switched off
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
Switch on DC main switch
493
DC relay is faulty
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
notify a Fronius-trained service engineer
494
Grounding fault on the control board
Behaviour
The inverter is not feeding any energy into the grid.
Remedy
notify a Fronius-trained service engineer