Fronius Agilo 75.0 User Manual
Page 38
36
2
3
Fixing the heavy-duty castors
(1)
Castor
(2)
Rubber stopper
*
Ways of accessing the heavy-duty
castors on the underside of the in-
verter
Counter-clockwise:
unscrew rubber stopper
Clockwise:
screw in rubber stopper
IMPORTANT! Secure all 4 of the inverter's heavy-duty castors. Unscrew the rubber stop-
per beyond the castor.
To prevent any subsequent distortion of the doors of the inverter, ensure that the inverter
is always absolutely level.
Any slight unevenness can be compensated for using the rubber stoppers.
Notes regarding
the air supply and
the connection of
an exhaust duct
The air supply to the inverter must be at least 1200 m³/h (approx. 20 m³/min).
When connecting an exhaust duct, the back pressure it causes must not exceed 150 Pa.
This results in a volumetric flow of about 15 m³/min.