Fronius Agilo 75.0 User Manual
Page 41
39
EN
3
-
Feed the AC cable into the inverter, ob-
serving the bending radii specified by
the cable manufacturer
-
Strip sheath from AC cable
-
Strip at least 20 mm of wire from phase
conductor L1 - L3, neutral conductor N
and ground conductor PE
-
Align phase conductors L1 - L3 and
neutral conductor N with the mains
connections according to the phase
-
Align the ground conductor PE with the
grounding terminal
-
Push the AC terminal over the phase
conductor, the neutral conductor and
the ground conductor
4
-
Push the AC terminal up and over the
mains connection and the bare end of
the cable
-
Tighten the AC terminal:
5 mm Allen key
Tightening torque = 12 Nm
-
Place the insulation caps onto the
mains connections
-
Repeat the process for phase conduc-
tors L2 and L3 and the neutral conduc-
tor N
5
-
Close the connection covers for the
mains connections
3
3
1
3
2
1
4x
L1
L2
L3
N
4
5