Fronius Agilo 75.0 User Manual
Page 77
75
EN
DC Mode
DC mode
FIX
Voltage value in V for fixed voltage operation
User
Voltage value in V for MPP User operation
Grid Monitoring:
GMTi
Start-up time of inverter in s
GMTr
Reconnection time in s following a grid fault
ULL
Mean grid voltage over 10 minutes in V.
LL Trip
Trip time for long-term voltage monitoring
Voltage Limits:
UIL max
Upper inner grid voltage in V
UIL min
Lower inner grid voltage in V
UOL max
Upper outer grid voltage limit value in V
UOL min
Lower outer grid voltage limit value in V
Frequency Limits:
FIL max
Upper inner grid frequency in Hz
FIL min
Lower inner grid frequency in Hz
FOL max
Upper outer grid frequency limit value in Hz
FOL min
Lower outer grid frequency limit value in Hz
LVFRT:
Status
Status of the LVFRT function (Low Voltage Fault Ride Through,
according to BDEW TR3 5.7)
DB min
Dead Band Value min.
Lower voltage limit as % for the reactive power feed
DB max
Dead Band Value max.
Upper voltage limit as % for the reactive power feed
k-Fac
Gradient showing how much reactive current is fed in as a func-
tion of voltage
P AC Reduction:
Max. P AC
Manual power reduction
GPIS
Softstart function
GFDPRv
Grid frequency-dependent power reduction in %/Hz
GFDPRr
Return to nominal output in %/s (following a grid frequency-in-
duced power reduction)