Fronius Agilo 75.0 User Manual
Page 112
110
Fronius Agilo
100.0-3
Input data
Output data
General data
Protection devices
MPP voltage range
460 - 820 V DC
Max. input voltage
(at 1000 W/m²/ -10 °C in an open circuit)
950 V DC
Max. input current
227.0 A
Max. short circuit current of the solar modules
340.5 A
Nominal output power (P
nom
)
100 kVA
Max. output power
100 kVA
Nominal grid voltage
3 ~ NPE 400 V / 230 V
Grid voltage tolerance
+10 / -5 %
1)
Nominal output current (three-phase)
150.2 A
Nominal frequency
50 - 60 Hz
1)
Total harmonic distortion
< 3 %
Power factor cos phi
1
0.8 - 1 ind./cap.
2)
Max. permitted mains impedance Z
max
at PCC
3)
52 mOHM
Max. feedback current
4)
0 A
5)
Starting current pulse
6)
0 A
5)
Max. output fault current per period
522 A / 2.47 ms
Maximum efficiency
97.2 %
Europ. efficiency
96.6 %
Overnight internal consumption
36 W
Cooling
Controlled forced-air ventilation
Degree of protection
IP 30
Dimensions l x w x h
1100 x 700 x 1884 mm
Weight
834 kg
Permitted ambient temperature
(at 95% rel. humidity)
- 20 °C - +50 °C
EMC emission class
A
Over-voltage category AC / DC
3 / 2
Degree of pollution
3
DC insulation measurement
Warning/shutdown
7)
at R
ISO
< 31.66 kOhm
Manifestation of DC overload
Operating point shift
power limitation
DC circuit breaker
Integrated