Fronius Agilo 75.0 User Manual
Page 92
90
Class 4 status
codes
Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
gineer.
Remedy
Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer
IMPORTANT! Due to the low level of insolation early in the morning and in the evening,
the status code 307 (DC low) is routinely displayed at these times of day. This status code
does not indicate any kind of fault.
309
DC input voltage too high
Behaviour
Short-term interruption while feeding energy into the grid
The inverter resumes with its startup routine.
Remedy
Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer
321
Overcurrent (AC)
Behaviour
Short-term interruption while feeding energy into the grid due to
a grid fault or a power module fault
The inverter resumes with its startup routine.
Remedy
Fault is rectified automatically
If this status code keeps recurring, contact your system engi-
neer
322
Overtemperature on the air intake sensor
Behaviour
Permanent interruption while feeding energy into the grid
Remedy
Reduce the ambient temperature and ensure that a suitable hot
air extractor is installed if necessary
If this status code keeps recurring, contact your system engi-
neer
401
No communication with power stage set possible
Behaviour
The inverter will automatically attempt to connect again and, if
possible, will resume feeding energy into the grid
Remedy
If the status code is displayed all the time: notify a Fronius-
trained service engineer
406
Power module temperature sensor defective
Behaviour
The inverter is disconnected from the grid for safety reasons.