FIELD SERVICE GUIDE

The problem most frequently encountered in refrigera-

tion systems is liquid water downstream. Most causes

of water carry-over can be identified and remedied by

using the FIELD SERVICE GUIDE. For further help,

contact Deltech.

DANGER

Refrigeration systems can be dangerous.

Work on the refrigeration system should be

done only by a competent refrigeration me-

chanic.

Do not release fluorocarbon refrigerants in-

doors or drain liquid refrigerants into floor

drains. Refrigerant vapors may accumulate

in low places. Inhalation of high concentra-

tions may be fatal. All refrigerant must be re-

covered per EPA requirements.

Do not smoke while working on the

refrigeration system or when a refrigerant

leak is suspected. Refrigerant may decom-

pose in the presence of burning materials,

forming toxic gas or acids which may cause

serious injury and property damage.

Pyramid 8000

®

Series Purifiers (Bulletin 289)

15

SYMPTOM

POSSIBLE CAUSE

REMEDY

No discharge from automatic

drain valves on coalescing filter.

Accumulation of dirt in automatic

drain valves or failure of auto-

matic drain valves.

Dismantle and clean, repair or replace automatic

drain valves (refer to Bulletin 138).

INLET AIR temperature indicating

light flashes, IAT is outside nor-

mal range or IAT reaches alarm

set point.

Aftercooler malfunction.

Check aftercooler discharge temperature. Reduce

temperature to 120°F max.; reduce airflow if tem-

perature is above 100°F (see Airflow section).

Refrigerant compressor stopped.

(REFRIG SUCTION temperature

light flashes, temperature is out-

side normal range or alarm set

point is reached.)

1. Fouled condenser.

1. Clean condenser coils (see Maintenance,

Monthly). Push reset button on high/low refrigerant

cutout control.

2. Refrigerant compressor over-

heated.

2. Ensure adequate ventilation of purifier. Motor

thermostat resets automatically. Turn off purifier,

wait 30 minutes, then restart.

3. Refrigerant compressor

inoperative.

3. Have refrigeration mechanic replace compres-

sor.

Refrigerant compressor stopped.

(REFRIG DISCHARGE tempera-

ture light flashes, temperature is

outside normal range or alarm

set point is reached.)

1. Refrigerant compressor

overheated.

1. Ensure adequate ventilation of purifier. Motor

thermostat resets automatically. Turn off purifier,

wait 30 minutes, then restart.

2. Refrigerant compressor

inoperative.

2. Have refrigeration mechanic replace compres-

sor.