NORMAL OPERATION — The green NORMAL

OPERATION indicator will light when the tempera-

ture inside the evaporator (chiller ) is normal.

CHECK OPERATING CONDITIONS — The red

CHECK OPERATING CONDITIONS indicator will

light when the temperature inside the evaporator is too

high.

SERVICE DUE — The yellow SERVICE DUE indi-

cator will light under three conditions: as a reminder to

perform routine maintenance after 4,500 hours of

dryer service (approximately six months), when a

thermocouple, or when a filter element must be

changed.

6

Pyramid 8000

®

Series Purifiers (Bulletin 289)

Table IV

System Operation Monitor Indicating Lights

INDICATING

LIGHT

INDICATES

ACTION REQUIRED

NOTES

NORMAL

OPERATION

The temperature inside the evapo-

rator (chiller) is normal.

This indicator should light within

30 minutes of start-up, after the re-

frigeration system has stabilized.

It should remain on when the

dryer is operating.

Indicator will go off if the CHECK

OPERATING CONDITIONS indica-

tor comes on or when a

thermocouple has failed.

CHECK

OPERATING

CONDITIONS

The temperature inside the

evaporator (chiller) is too high.

It is normal for this light to be on

when the dryer is first turned on

and remain on until the dryer has

reached normal operating tem-

peratures (about 30 minutes).

If the CHECK OPERATING CON-

DITIONS indicator turns on during

normal operation, turn the dryer

off to avoid compressor damage.

Have a refrigeration mechanic

identify and correct the malfunc-

tion. If the dryer is under warranty,

call your local distributor for

authorization before servicing

Indicator will remain illuminated

until problem has been corrected.

SERVICE

DUE

1. 4,500 hours of dryer service

(approximately six months) has

passed; routine maintenance

should be performed.

1. See maintenance section in this

manual for further instructions.

See maintenance section in this

manual for instructions on reset-

ting indicator.

2. A thermocouple is sensing tem-

perature outside of normal range

or it has failed. The thermocouple

may sense temperatures outside

of normal range for up to two min-

utes after startup or in extreme

temperature conditions. (The al-

phanumeric display will read T1,

T2, T3, T4 or T5 MALFUNCTION.

T1 = inlet air, T2 = refrigerant

suction, T3 = refrigerant dis-

charge, T4 = ambient air, T5 =

evaporator.)

2. Check thermocouple. Replace

if necessary.

Indicator will go off when the dryer

is turned off. This will not affect

the 4,500 hour routine mainte-

nance indicator.

3. Pressure drop across the prefil-

ter/separator or particulate after

filter indicates the need to replace

element.

Alphanumeric display reads CHG

SEPARATOR or CHG PARTICU-

LATE.

1. See maintenance section in this

manual for further instructions.

Indicator will reset when pressure

drop returns to normal..

SYSTEM

ALARM

1. Inlet air temperature is too high.

Determine which temperature(s) is

out of range. See the Field Serv-

ice Guide in this manual for possi-

ble causes/remedies

Indicator will not stop flashing un-

til the problem has been cor-

rected.

2. Refrigerant suction temperature

is too low.
3. Ambient air temperature is too

low.
4. Ambient air temperature is too

high.