Flowserve CPXV fitted with WW User Manual
Page 17

CPXV - WW/CW USER INSTRUCTIONS ENGLISH 85392698 10-09
Page 17 of 36
flowserve.com
5.2.5.2 Grease lubricated bearings 
When grease nipples are fitted, one charge between 
grease changes is advisable for most operating 
conditions; ie 2 000 hours interval. Normal intervals 
between grease changes are 4 000 hours or at least 
every 6 months. 
 
The characteristics of the installation and severity of 
service will determine the frequency of lubrication. 
Lubricant and bearing temperature analysis can be 
useful in optimizing lubricant change intervals. 
 
The bearing temperature may be allowed to rise to 
55 ºC (99 ºF) above ambient, but should not exceed 
95 ºC (204 ºF). For most operating conditions, a 
quality grease having a lithium soap base and NLGI 
consistency of No 2 or No 3 is recommended. The 
drop point should exceed 175 ºC (350 ºF). 
Never mix greases containing different
bases, thickeners or additives. 
 
5.3 Impeller clearance
This is preset - see section 6.7, Setting impeller 
clearance. 
 
5.4 Direction of rotation
Serious damage can result if the pump
is started or run in the wrong direction of rotation. 
 
The pump is shipped with the coupling element 
removed. Ensure the direction of rotation of the motor is 
correct before fitting the coupling element. Direction of 
rotation must correspond to the direction arrow. 
If maintenance work has been carried
out to the site's electricity supply, the direction of 
rotation should be re-checked as above in case the 
supply phasing has been altered. 
 
5.5 Guarding
Guarding is supplied fitted to the pump set.
Fasteners for guards must remain captive in the guard 
to comply with the Machinery Directive 2006/42/EC. 
When releasing guards, the fasteners must be 
unscrewed in an appropriate way to ensure that the 
fasteners remain captive. Whenever guarding is 
removed or disturbed ensure that all the protective 
guards are securely refitted prior to start-up. 
 
5.6 Priming and auxiliary supplies
 
5.6.1 Filling and priming 
The pump end needs to be completely
submerged in the product. 
 
5.6.2 Auxiliary supplies 
Ensure all electrical, hydraulic,
pneumatic, sealant and lubrication systems (as 
applicable) are connected and operational. 
 
5.6.3 Pumps fitted with a heating jacket 
The pump should be pre-heated for at
least one hour using steam through the heating jacket 
before hot liquid is brought into the pump. The 
quantity, temperature and pressure can be obtained 
from the dimensional drawing. This action is 
important to avoid distortion and maintain the gap 
between impeller and casing. 
 
Ensure pump is electrically isolated. Then before 
starting the driver rotate the shaft several times by 
(gloved) hand to ensure freedom of rotation as the high 
temperature will cause expansion and the increase in 
lengths of the components should be identical. 
 
5.7 Starting the pump
a)
Ensure flushing and/or cooling/
heating liquid supplies are turned ON, before 
starting pump. 
b) CLOSE the outlet valve partially, but ensure that
air is allowed to escape out of the discharge pipe. 
This is especially important for pumps with 
product lubricated line bearings. 
c)
Ensure that the liquid level in the
sump is above the minimum pump casing 
submergence level. 
d)
Ensure all vent valves are closed
before starting.
e) Start motor and check the outlet pressure. 
f) If the pressure is satisfactory, SLOWLY open the 
outlet valve.
g)
Do not run the pump with the outlet
valve completely closed.
h) If NO pressure, or LOW pressure, STOP the pump.
Refer to section 7, Faults; causes and remedies for 
fault diagnosis. 
