Flowserve S-series PolyChem User Manual
Page 23

USER INSTRUCTIONS POLYCHEM S-SERIES ENGLISH 71569207 11-08
Page 23 of 52
flowserve.com
4.7 Electrical connections
Electrical connections must be made
by a qualified Electrician in accordance with relevant 
local national and international regulations. 
A device to provide emergency stopping must
be fitted. If not supplied pre-wired to the pump unit, 
the controller/starter electrical details will also be 
supplied within the controller/starter. For electrical 
details on pump sets with controllers see the 
separate wiring diagram. 
It is important to be aware of the EUROPEAN
DIRECTIVE on potentially explosive areas where 
compliance with IEC60079-14 is an additional 
requirement for making electrical connections. 
It is important to be aware of the EUROPEAN
DIRECTIVE on electromagnetic compatibility when 
wiring up and installing equipment on site. Attention 
must be paid to ensure that the techniques used during 
wiring/installation do not increase electromagnetic 
emissions or decrease the electromagnetic immunity of 
the equipment, wiring or any connected devices. If in 
any doubt contact Flowserve for advice. 
The motor must be wired up in
accordance with the motor manufacturer's 
instructions (normally supplied within the terminal 
box) including any temperature, earth leakage, 
current and other protective devices as appropriate. 
The identification nameplate should be checked to 
ensure the power supply is appropriate. 
See section 5.4, Direction of rotation,
before connecting the motor to the electrical supply. 
 
4.8 Final shaft alignment check
a) Level baseplate if appropriate. 
b) Mount and level pump if appropriate. Level the 
pump by putting a level on the discharge flange. 
If not level, adjust the footpiece by adding or 
removing shims [3126.1] between the footpiece 
and the bearing housing. 
c) Check initial alignment. If pump and driver have
been remounted or the specifications given below 
are not met, perform an initial alignment as 
described in section 4.5. This ensures there will 
be sufficient clearance between the motor hold 
down bolts and motor foot holes to move the 
motor into final alignment. The pump and driver 
should be within 0.38 mm (0.015 in.) FIM (full 
indicator movement) parallel, and 0.0025 mm/mm 
(0.0025 in./in.) FIM angular. 
Stilt mounted baseplates 
If initial alignment cannot be achieved with the 
motor fasteners centered, the baseplate may be 
twisted. Slightly adjust (one turn of the adjusting 
nut) the stilts at the driver end of the baseplate 
and check for alignment to the above tolerances. 
Repeat as necessary while maintaining a level 
condition as measured from the pump discharge 
flange. 
d) Run piping to the suction and discharge to the
pump. There should be no piping loads 
transmitted to the pump after connection is made. 
Recheck the alignment to verify that there are no 
significant changes. 
e) Perform final alignment. Check for soft-foot under
the driver. An indicator placed on the coupling, 
reading in the vertical direction, should not indicate 
more than 0.05 mm (0.002 in.) movement when 
any driver fastener is loosened. Align the driver 
first in the vertical direction by shimming 
underneath its feet. 
f) When satisfactory alignment is obtained the
number of shims in the pack should be minimized. 
It is recommended that no more than five shims be 
used under any foot. Final horizontal alignment is 
made by moving the driver. Maximum pump 
reliability is obtained by having near perfect 
alignment. Flowserve recommends no more than 
0.05 mm (0.002 in.) parallel, and 0.0005 mm/mm 
(0.0005 in./in.) angular misalignment. (See 
section 6.8.4.7.) 
g) Operate the pump for at least an hour or until it
reaches final operating temperature. Shut the 
pump down and recheck alignment while the pump 
is hot. Piping thermal expansion may change the 
alignment. Realign pump as necessary. 
4.9 Protection systems
The following protection systems are
recommended particularly if the pump is installed in a 
potentially explosive area or is handling a hazardous 
liquid. If in any doubt consult Flowserve. 
 
If there is any possibility of the system allowing the 
pump to run against a closed valve or below 
minimum continuous safe flow a protection device 
should be installed to ensure the temperature of the 
liquid does not rise to an unsafe level. 
 
If there are any circumstances in which the system 
can allow the pump to run dry, or start up empty, a 
power monitor should be fitted to stop the pump or 
prevent it from being started. This is particularly 
relevant if the pump is handling a flammable liquid. 
