4 grouting – Flowserve S-series PolyChem User Manual
Page 16

USER INSTRUCTIONS POLYCHEM S-SERIES ENGLISH 71569207 11-08
Page 16 of 52
flowserve.com
k) It should be noted that the connecting pipelines
must be individually supported, and that the 
spring mounted baseplate is not intended to 
support total static pipe loads. 
Figure 4-4
1. Stilt b olt
2. Bottom spring [3¼ in. 
(83 mm) O/D x 4 in. 
(102 mm) fl oor cups] 
3. Top spring [2 in.
(51 mm) O/D x 4 in. 
(102 mm) flo or cu ps] 
4. Nuts 
5. Flat w asher 
6. Lock wash er 
7. Floor cup 
1 i n. (25 mm) a pprox. i nitial h eigh t
4.3.3.3 Stilt/spring mounted baseplates - motor 
alignment 
The procedure for motor alignment on stilt or spring 
mounted baseplates is similar to grouted baseplates. 
The difference is primarily in the way the baseplate is 
levelled. 
a) Level the baseplate by using the stilt adjusters. 
(Shims are not needed as with grouted baseplates.)
b) After the base is level, it is locked in place by
locking the stilt adjusters.
c) Next the initial pump alignment must be checked.
The vertical height adjustment provided by the 
stilts allows the possibility of slightly twisting the 
baseplate. If there has been no transit damage 
or twisting of the baseplate during stilt height 
adjustment, the pump and driver should be within 
0.38 mm (0.015 in.) parallel, and 0.0025 mm/mm 
(0.0025 in./in.) angular alignment. If this is not 
the case, check to see if the driver mounting 
fasteners are centered in the driver feet holes. 
d) If the fasteners are not centered there was likely
shipping damage. Re-center the fasteners and 
perform a preliminary alignment to the above 
tolerances by shimming under the motor for 
vertical alignment, and by moving the pump for 
horizontal alignment. 
e) If the fasteners are centered, then the baseplate
may be twisted. Slightly adjust (one turn of the 
adjusting nut) the stilts at the driver end of the 
baseplate and check for alignment to the above 
tolerances. Repeat as necessary while 
maintaining a level condition as measured from 
the pump discharge flange. 
f) Lock the stilt adjusters. 
The remaining steps are as listed for new grouted 
baseplates. 
4.4 Grouting
a) The pump foundation should be located as close to
the source of the fluid to be pumped as practical.
b) There should be adequate space for workers to
install, operate, and maintain the pump. The 
foundation should be sufficient to absorb any 
vibration and should provide a rigid support for 
the pump and motor. 
c) Recommended mass of a concrete foundation
should be three times that of the pump, motor 
and base. Refer to Figure 4-5. 
Foundation bolts are imbedded in the
concrete inside a sleeve to allow some 
movement of the bolt. 
Figure 4-5
d) Level the pump baseplate assembly. If the
baseplate has machined coplanar mounting 
surfaces, these machined surfaces are to be 
referenced when leveling the baseplate. This may 
require that the pump and motor be removed from 
the baseplate in order to reference the machined 
faces. If the baseplate is without machined 
coplanar mounting surfaces, the pump and motor 
are to be left on the baseplate. The proper surfaces 
to reference when leveling the pump baseplate 
assembly are the pump suction and discharge 
flanges. DO NOT stress the baseplate. 
e) Do not bolt the suction or discharge flanges of the
pump to the piping until the baseplate foundation is 
completely installed. If equipped, use leveling 
jackscrews to level the baseplate. If jackscrews are 
not provided, shims and wedges should be used. 
(See Figure 4-5.) Check for levelness in both the 
longitudinal and lateral directions. Shims should be 
placed at all base anchor bolt locations, and in the 
middle edge of the base if the base is more than 
1.5 m (5 ft.) long. Do not rely on the bottom of the 
baseplate to be flat. Standard baseplate bottoms 
are not machined, and it is not likely that the field 
mounting surface is flat. 
