Amps AC (AAC) TrueRMS (50-60Hz)
Test any isolated power line. Select AAC/Hz dial position.
Ranges: 0 to 400AAC Resolution: 0.1A Crest factor: ≤ 3
Accuracy: ±(2.0% + 5dgts) 50-60Hz
Jaw Opening: 1.2in (30 mm) Overload Protection: 400AAC
Frequency (Hz) Through Clamp
Measure frequency without using test leads, just use the clamp.
Turn dial to AAC/Hz and press SEL. Clamp Hz will be displayed.
Range: 20Hz to 400Hz Accuracy: ±(0.5% + 5)
Minimum current range: > 5AAC at 20 to 100Hz, >10AAC at 100
to 400Hz Resolution: 0.1Hz Overload Protection: 400AAC
Resistance (Ω)
Used for “ohming out” a motor. 0.1Ω resolution is necessary to
test the resistance between the motor poles because the values are
typically very low. Select MFD/Ω/
O
F
F
MFD
NCV
V
AC
V
DC
A
AC
Hz
Hz
%
°C
°F
SC56
AUTO OFF
TRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
SEL
HOLD
INRUSH
and press SEL button once.
Ranges: 0 to 1000Ω, 1000Ω to 9999Ω
Resolution: 0.1Ω Overload Protection: 600VDC/VAC rms
Accuracy: ±(1.5% + 5)
Continuity (
O
F
F
MFD
NCV
V
AC
V
DC
A
AC
Hz
Hz
%
°C
°F
SC56
AUTO OFF
TRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
SEL
HOLD
INRUSH
)
Use the continuity feature to test if a circuit is open or closed. Use
this feature to check fuses as well. A steady “beep” and green LED
indicate the circuit is good. Select MFD/Ω/
O
F
F
MFD
NCV
V
AC
V
DC
A
AC
Hz
Hz
%
°C
°F
SC56
AUTO OFF
TRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
SEL
HOLD
INRUSH
and press SEL twice.
Range: 1000Ω Resolution: 0.1Ω Response time: 100ms
Audible beep: <30Ω Overload Protection: 600VDC/VACrms
Non Contact Voltage (NCV)
Use the non contact voltage (NCV) feature to test if a wire is hot
or not. Always test on a known live source before using. A red LED
blinks and beeping sound is emitted at voltages >24VAC
AC Voltage Detection Range: 24VAC to 600VAC (50-60Hz)
Temperature (°F/°C)
Plug any K-type thermocouple directly into the meter to measure
temperature. Cold junction is located inside the meter and allows for
extremely accurate measurements even in rapidly changing ambient
temperatures (going from rooftop to freezer). No adapter is required.
See Temp Calibration section for calibration instructions.
Range: -40°F to 2200°F, (-40°C to 1200°C) Resolution: 0.1°
Accuracy: ±(1°F) 32°F to 120°F, ±(1°C) 0°C to 49°C
±(1%+2°F) 120°F to 750°F, ±(1%+1°C) 49°C to 400°C
±(2%+6°F) -40°F to 32°F, ±(2%+3°C) -40°C to 0°C
±(2%+6°F) 750°F to 2200°F, ±(2%+3°C) 400°C to 1200°C
Sensor type: K-type thermocouple
Overload protection: 30 VDC or 30VAC rms
Temp. Calibration
For accuracies of ±1°F,
calibrate to a known
temperature. A glass
of stabilized ice water
is very close to 32°F
(0°C) and is usually very
convenient but any
known temperature can
be used.
1. Select the °F/ °C range.
2. Plug thermocouple to be
calibrated into the K-type jack.
3. Unscrew A and B and remove
the battery cover.
4. Stabilize a large cup of ice
water. Stir the ice with the
water until temperature stays at
32°F (0°C).
5. Immerse the thermocouple
probe and let it stabilize. Keep
stirring to prevent micro-
environments.
6. Use a small screwdriver to
adjust calibration pot C to the
right of the battery as close to
32°F as you would like.
Modular
Expandability
Your Swivel Clamp Meter is compatible with
all Fieldpiece Accessory Heads. With Fieldpiece
Accessory Heads, you can measure any
available parameter, and read the measurement
on your meter's display in real-time.
Just set the range to mVDC. Pressing SEL
changes the mV range. Remove the probe tips
of your test leads, and connect your accessory
head (model AAV3 shown).
Visit www.fieldpiece.com to see all of the
different accessory heads that Fieldpiece offers.
Safety Features
1. Bright LED and beeper warn you when testing
voltages above 30V.
2. Switch to the NCV function (non contact volt-
age) and point clamp claw towards suspected
voltage source. Monitor the bright LED and
beeper to see if the source is “hot.”
3. Rotate the clamp to the angle that best suits
the situation.
4. Temp switch to prevent leaving thermocouple
plugged in while measuring voltage.
BatteryReplacement
The battery must be replaced when the
battery icon is empty. "bAtt" will display with a
beeping sound. Meter will shut off in 5 seconds.
Disconnect and unplug leads, turn meter off
and remove battery cover.
Safety Information
• Never ground yourself when taking electrical
measurements. Do not touch exposed metal
pipes, outlets, fixtures, etc., which might be at
ground potential, while taking measurements.
Keep your body isolated from ground by us-
ing dry clothing, rubber shoes, rubber mats,
or any approved insulating material.
• Disconnect the test leads before opening the
case. Inspect the test leads for damage to the
insulation or exposed wire. Replace if suspect.
Keep your fingers behind the finger guards on
the probes while taking measurements.
• When disconnecting from a circuit, disconnect
the “RED” lead first, then the common “BLACK”
lead. Use one handed testing when possible.
Work with others.
• Turn off power to the circuit under test before
cutting, unsoldering, or breaking the circuit.
• Do not measure resistance (ohms) when cir-
cuit is powered. Isolate load by disconnecting
from circuit.
• Disconnect the meter from the circuit before
turning any inductor off, including motors,
transformers, and solenoids. High voltage
transients can damage the meter beyond
repair. Do not use during electrical storms.
• Do not apply more than rated voltages be-
tween input and ground.
• Isolate capacitors from system and discharge
them safely before testing.
All voltage tests: All voltage ranges will
withstand up to 600V. Do not apply more than
600VDC or AC rms.
Symbols used:
Caution, risk of electric shock
Caution, refer to manual.
Ground
Double insulation
Maintenance
Clean the exterior with a dry cloth. Do not
use liquid.
Limited Warranty
This meter is warranted against defects in
material or workmanship for one year from
date of purchase. Fieldpiece will replace or
repair the defective unit, at its option, subject
to verification of the defect.
This warranty does not apply to defects
resulting from abuse, neglect, accident,
unauthorized repair, alteration, or unreasonable
use of the instrument.
Any implied warranties arising from the sale of
a Fieldpiece product, including but not limited
to implied warranties of merchantability and
fitness for a particular purpose, are limited to
the above. Fieldpiece shall not be liable for loss
of use of the instrument or other incidental or
consequential damages, expenses, or economic
loss, or for any claim of such damage, expenses,
or economic loss.
State laws vary. The above limitations or
exclusions may not apply to you.
Obtaining Service
Call Fieldpiece Instruments for one-price-
fix-all out-of-warranty service pricing. Send
check or money order for the amount quoted.
Send the meter freight prepaid to Fieldpiece
Instruments. Send proof of date and location
of purchase for in-warranty service. The meter
will be repaired or replaced, at the option
of Fieldpiece, and returned via least cost
transportation.
www.fieldpiece.com
© Fieldpiece Instruments, Inc 2012; v04
A
B
C
O
F
F
O
F
F
SE
L
RN
G
O
F
F
SE
L
RN
G
AUTO OFF
TRUE RMS
CAT III
600V
TEMP
K-TYPE
30V
MAX
Unplug Leads and Slide
TEMP Switch to the Right
O
F
F
!
WARNINGS
DISCONNECT AND UNPLUG TEST LEADS before opening case.
TEST NCV FUNCTION ON KNOWN LIVE WIRE before using.
DO NOT APPLY VOLTAGE greater than 30VAC or 60VDC to the
thermocouple or the jacks when the rotary dial is on °F. (Use
only k-type thermocouples)
REMOVE THE THERMOCOUPLE when taking voltage measurements.
DISCONNECT TEST LEADS when measuring temperature.
DO NOT APPLY VOLTAGE TO THE JACKS when the rotary dial is on
microamps. Even low voltages can cause a current overload and
potentially harm the meter.
!
SEL
RNG
Air Velocity
& Temperature
Head
English
READ
LO BATT
ON
LCD X
100
Average
(16 sec)
Metric
Real
time
AAV3
AUTO-
OFF
English
Metric
Ft/min
M/s
KM/hr
MPH
ºF
ºC
OFF
O
F
F