Remote device assignment configuration web page – DNF Controls USP-RDC User Manual
Page 6
Page 6 of 13
2.
REMOTE DEVICE ASSIGNMENT Configuration Web Page
Please note-
The USP will transmit messages only to the specified IP address listed in the Remote Device
Assignment Table.
The USP will accept messages only from GTP-32 /DC20s whose IP addresses are entered in the
Remote Device Assignment Table. The sender’s IP address must match the entry in the table.
NOTE- Redundant Mode of operation is enabled at powerup.
Use a USP key to turn Redundant Mode On/Off.
Remote Device Label Enter any 32 characters. This label is for convenience only and is used in the Event
Action Table.
Device Type GTP-32/DC20- Use to connect to DNF Controls GTP-32 and DC20 devices
Primary / Backup Pair Assign Remote Device to a Primary / Backup Pair #1 or Pair #2.
Assign Remote Device as Primary or Backup within pair.
Connection Type Not Used
Connection Mode Not Used
UDP Attempts Not Used
IP Address GTP-32 / DC20 IP address
Port Number Not Used
Heartbeat Rate Default value is 5 seconds. Communication error is defined as a loss of two consecutive
heartbeats.
Connection Status ------------------- Not connected
Connected
Connected to GTP-32/DC20 Device