Installation with Ground and Neutral Conductors Provided
For this type of installation, the power cable must contain an isolated earth-ground
conductor. Under this circumstance, do not connect neutral to ground at the
disconnect or at the display. This would violate electrical codes and void the
warranty. Use a disconnect so that all hot lines and neutral can be opened. Refer to

Figure 19

for installation details. The National Electrical Code requires the use of a

lockable power disconnect within sight of or at the sign.

Figure 19: Installation with Ground and Neutral Conductors Provided

Installation with Only a Neutral Conductor Provided
Installations where no grounding conductor is provided must comply with article
250-32 of the National Electrical Code. If the installation in question meets all of the
requirements of article 250-32, the following guidelines must be observed:

• Connect the grounding electrode cable at the local disconnect, never at the

sign panel board.

• A disconnect that opens all of the ungrounded phase conductors should be

used.

• The neutral and the ground conductors should be bonded in the sign panel

board.


Refer to

Figure 20

for installation details.

Figure 20: Installation with Only A Neutral Conductor Provided