beautypg.com

2 main window, 1 basic controls, Ain window – Bronkhorst FlowPlot User Manual

Page 7: Basic controls

background image

BRONKHORST

®

In realtime mode FlowPlot will ask FlowDDE for actual values at the same interval as the realtime poll time, unless the

sample time is manually set in FlowPlot. By default, the realtime poll time in FlowDDE is 25 ms and normally should

not be changed.

The Graph update time in the Options window in FlowPlot indicates how often FlowPlot will update the graph. Default

this is set to 200 ms, but on fast PCs it may be set lower for smoother plotting.

Setting

Short, fast measurement (<=600 s)

Long, slow measurement (>600 s)

Fast changes visible

Fast changes not visible

FlowDDE Poll time

100 ms (or lower for small systems)

100 ms

FlowDDE Realtime poll time

25 ms

25 ms

Scantime

15 ms

15 ms

Data acquistion time

auto

500 ms

Graph update time

200 ms (or lower on fast PCs)

500 ms

The poll times described here are not exact sample times. Therefore, the sample rate is not constant.

It is not necessarily true that FlowDDE will poll for new values exactly once per poll time. Also, the time-

stamp information from the interface will contain a millisecond value at which the data reached it.

For data acquisition and signal processing this is not an ideal situation, since most standard signal

processing functions require a constant sample rate.

2.2

M

AIN WINDOW

The main window is divided into several areas. The graph with all plots is presented in the largest. To the right of the

graph, below the legend, most controls are located.

2.2.1

Basic controls

Three controls are used to control the plot. Start will start acquiring data and plotting the graph and Stop will stop it.

Clear will clear the graph and remove the actual plot lines, but plotting continues from 0.

Page 7

FlowPlot

9.17.030