BayTech ATS Power Switching units 2012 User Manual

Page 18

background image

Page

18 

Identify Current User




Unit Identification




Setting Source Input Primary



SETUP OPTIONS 

ATSSET



Default Set Points

Loss Of Primary Source Power

(LOSSPSP)

Brownout

(Config option 6)

1 - 2

2 - 1

1 - 2

2 - 1

100V 66.6V 91.7V 77.3V 83.2V
110V 73.2V 100.9V 85.1V 91.5V
120V 79.9V 110.1V 92.8V 99.8V
200V 133.2V 183.4V 154.7V 166.4V
208V 138.2V 190.8V 160.9V 173.1V
220V 146.5V 201.8V 170.2V 183.0V
230V 153.1V 210.9V 177.9V 191.4V
240V 159.8V 220.1V 185.6V 199.7V

Frequency Set









Current User: root

Type Whoami at the prompt to determine the current user, the unit will display the
following:
To change the user, logout of the unit and log back in using the new user name.

Type Unitid at the prompt to determine the Unit ID, the unit will display the following:
To change the unit ID, Go to the Outlet Configuration menu and select “Change Unit
ID’ option. The maximum field length is 32 or 16 for older unit.

Unit ID: ATS18

Type ATSSET at the prompt, sets the pre-defined switch over points for power loss
and brownout. The preset values are listed below:

The menu displays the current operating frequency and then asks
the operator to choose the frequency. If no change is required
press “Enter”, otherwise select the appropriate number. Type
“X” to exit the ATSSET routine.

ATS>atsset

Current operating frequency is: 60 Hz
Enter operating frequency

1)...60 Hertz
2)...50 Hertz
X)...Exit

Enter(1-2,X):

Type source ‘n’, (n= 1 or 2) at the ATS> prompt. This will change the input to the
source selected and make it the primary input.

This manual is related to the following products: