Ul certification, Specifications, Control power – Basler Electric RDP-110 User Manual
Page 10: Communication, Audible alarm, Temperature, Weight, Type test data
![background image](https://www.manualsdir.com/files/773963/content/doc010.png)
2
9318100990 Rev H
UL Certification
An RDP-110 may be certified as “UL recognized” or “UL listed”. These certifications are specified by part
number as shown in Table 1.
Table 1. RDP-110 UL Certification Part Numbers
UL Certification
RDP-110 Style
RDP-110 Part Number
Recognized
F1
9318100115
Listed
F1
9318100119
Recognized
S1
9318100114
Listed
S1
9318100120
Specifications
RDP-110 electrical and physical characteristics are listed in the following paragraphs.
Control Power
DC Input
Range:
8 to 32 Vdc
Burden:
2 W maximum
AC Input
Range:
84 to 144 Vac
Burden:
5 VA maximum
Communication
The RDP-110 communicates through a serial, RS-485 port terminated with a 100
Ω resistor.
Audible Alarm
Frequency:
2,900 Hz, ±500 Hz
Sound Level:
90 dB(A) at 24 in (61 cm)
Temperature
Operating Temperature Range:
–40 to 70
°C (–40 to 158°F)
Storage Temperature Range:
–40 to 85
°C (–40 to 185°F)
Weight
3 kg (6.6 lb)
Type Test Data
Dielectric Strength
Withstood 1,800 Vdc for 1 minute between chassis ground and ac control power input. Withstood 700 Vdc
for 1 minute between any combination of the following circuit groups:
•
Chassis ground
•
DC control power input and RS-485 terminals
•
AC control power input
Radio Frequency Interference
Tested using a 5 W, handheld transceiver operating at random frequencies centered around 144 MHz
and 440 MHz with the antenna located within 6 inches (15 centimeters) of the device in both the vertical
and horizontal planes.
11BGeneral Information
RDP-110