17
Specifications
CBS 212A Current Boost Systems have the following features and capabilities.
Operational Specifications
Output Power
Voltage ....................................... 60/120/220 Vdc (controlled by position of Output Limit Select jumpers)
Current ....................................... 20 Adc
Sensing Voltage
Nominal Level ............................ 120/240 Vac (jumper selectable)
Frequency .................................. 50/60 Hz
Voltamperes ............................... 10 VA
Output Limiting
Output Selection ......................... 60, 120, or 220 Vdc (jumper selectable)
Adjustment Range ...................... 50 to 100% of selected output
Operation Point Adjustment Range
120 V Nominal ............................ 70 to 131 Vac
240 V Nominal ............................ 140 to 262 Vac
Dropout Ratio
120 V Nominal ............................ 5 V above pickup point
240 V Nominal ............................ 10 V above pickup point
Power Dissipation
At Continuous Rating ................. < 50 W
General Specifications
Type Tests
Shock ......................................... 15 G in each of three mutually perpendicular planes
Vibration ..................................... 5 to 26 Hz at 1.2 G
26 to 52 Hz at 0.036” (0.914 mm), double amplitude
52 to 260 Hz at 5 G
Temperature
Operating....................................
−40°F to 140°F (−40°C to 60°C)
Storage .......................................
−85°F to 185°F (−65°C to 85°C)
Знак ЕАС (соответствие евразийским нормам)
•
TP TC 004/2011
•
TP TC 020/2011
Данный продукт рассчитан на 20 лет эксплуатации и хранения при условии соблюдения
инструкций настоящего руководства.
CBS 212A
Specifications