Current Transformers (CTs)
Six standard CTs are available for 600 volt (or less) systems. The CTs should be mounted as close to the
generator output terminals as practical and before any load devices such as power transformers and
circuit breakers. Table 2 lists the available CTs and their corresponding ratios and short-circuit line-
current ratings. Mounting and drilling dimensions for each of the six CTs are provided in Figures 4 through
9. For applications with system voltages higher than 600 volts, contact Basler Electric.
Table 2. CT Data
CT Part Number
Turns Ratio
3-Phase Short-Circuit
Line Current
*
BE25925001 †
1:8
125 to 250 A
BE25926001 †
1:17
250 to 500 A
BE25927001 †
1:34
500 to 1,000 A
BE25928001 †
1:69
1,000 to 2,000 A
BE25929001 †
1:138
2,000 to 4,000 A
BE25930001 †
1:277
4,000 to 8,000 A
* All current values represent 300% short-circuit values.
† These CTs have pre-wound primary windings (no conductor window).