beautypg.com

Motor voltage, Contact sensing inputs, Motor voltage -7 – Basler Electric BE1-79A User Manual

Page 47: Contact sensing inputs -7, Figure 5-6. contact sensing jumpers, Figure 5-7. contact sensing jumper locations

background image

9310200990 Rev J

BE1-79A Installation and Configuration

5-7

Motor Voltage

No adjustment is required for the motor voltage applied at terminals 5 and 6. The applied voltage can

range from 120 to 240 Vac or 125 to 250 Vdc. These terminals serve as the input to the BE1-79A power

supply and control functions.

Contact Sensing Inputs

Energizing levels for contact sensing inputs V1 through

V4 are jumper selectable for operation at three nominal

voltage levels. Jumper P3 controls the operating voltage

for V1, P4 controls V2, P5 controls V3, and P6 controls

V4. Nominal voltage levels of 125 Vdc/120 Vac, 48 Vdc,

or 250 Vdc/240 Vac may be selected. Figure 5-6

illustrates the three possible jumper positions for P3

through P6. Input V5 is dedicated to monitoring the relay

power supply input and is not jumper selectable.

Figure 5-6. Contact Sensing Jumpers

NOTE

In certain applications where 240 Vac control voltage is used, control circuit

feedback can occur through system inductive coupling. This feedback can

result in erroneous signals, causing relay operation. If there is a potential for

control circuit feedback, the jumper selectable voltage range should be

changed from the 48 Vdc factory default setting to a higher position. Selections

are provided in Table 3-1.


The following paragraphs describe how to locate and change the position of the contact-sensing jumpers.
1. Remove the four Phillips screws from the front panel and separate the front panel from the relay

chassis.

2. Carefully grasp and remove the Digital circuit board (top circuit board) from the relay chassis. Take

care not to damage any of the circuit board components. Observe all electrostatic discharge (ESD)

precautions when handling the circuit board. Place the circuit board on an ESD-safe surface.

3. Locate the four jumper terminal blocks (P3 through P6) on the circuit board. The jumper terminal

blocks are located on the component side of the circuit board near the rear contact fingers (see

Figure 5-7). Each terminal block has three pins and each jumper is factory installed on pins 2 and 3.

Figure 5-6 illustrates each of the three jumper positions.

Figure 5-7. Contact Sensing Jumper Locations


4. To select operation at 125 Vdc or 120 Vac, remove the jumper from pins 2 and 3 and position it on

pins 1 and 2. To select operation at 250 Vdc or 240 Vac, remove the jumper from pins 2 and 3 and

position it on pin 3 for storage. (Only pin 3 of the terminal block should be covered.)