beautypg.com

Reset, Lockout, Reclosing sequences – Basler Electric BE1-79A User Manual

Page 30: Reset -8, Lockout -8, Reclosing sequences -8

background image

3-8

BE1-79A Functional Description

9310200990 Rev J

Reset

A reclosing sequence may be initiated only when the relay is in the reset state. Reset is indicated by the

front panel Reset LED. In order for the relay to reach reset, the controlled breaker must be closed during

a three-second period when the reset timer expires. If the breaker opens prior to this time, the relay will

proceed to the next reclosing attempt. If the number of programmed reclosing attempts has been

exhausted, the relay will drive to lockout.
A reset time of zero is used if no reset is desired after a specific reclosing attempt. As an example, for a

first reclose/reset time delay setting of SP-79A1=10,0, the 0 indicates that the BE1-79A will not reset until

after the next non-zero reset time. If the second reclose/reset time delay setting is SP-79A2=30,40, then

the relay will reset at the 40 second point in the timing sequence.

Lockout

Lockout, a state inhibiting relay operation, may be produced by four conditions:

Reclose failure

Number of breaker openings exceeds the number of programmed reclosure attempts

The EXIT command is entered to terminate RS-232 communication

Communication access has timed out

Lockout is indicated by the front panel Lockout LED. The S-ALM command allows output C3 to be

programmed to close for a lockout condition. Lockout is terminated when the controlled breaker is closed

(manually or by other means) and remains closed for the duration of the final reset time delay setting.

Reclosing Sequences

A reclosing sequence is initiated by the closure of a 52b contact. A reclosing sequence is indicated by the

In Sequence LED located on the front panel. The BE1-79A provides up to four automatic reclosures.

Each reclose setting is adjustable and has a setting range of 0 to 300 seconds. The number of reclosing

attempts may be limited by adjusting any one of the reclose time delay settings (after the first reclose) to

zero. When a breaker trip occurs at this point in the reclosing sequence, the BE1-79A will time toward

lockout. An instantaneous first reclose is enabled on BE1-79A relays configured for ACR11B operation by

an external jumper connected across case terminals 13 and 17 or by switch S4 located on the right side

of the relay cradle.
Each of the four reclose settings has a corresponding reset timer. A final reset controls the time between

lockout and reset. Each reset setting is adjustable and has a setting range of 0 to 300 seconds. Pressing

the front panel Reset pushbutton will clear a reclosing sequence and return the relay to the reset state.
The numbering and labeling of reclose and reset timer settings of Basler reclosing relays such as the

BE1-79 and BE1-79M are based on the breaker opening that immediately precedes each reclose and

reset setting. This is not the case with the BE1-79A. Each reclose and reset timer setting begins at time

zero when the breaker opens the first time and initiates the first reclose timer. Typically, this makes the

first reclose setting the shortest time setting and the fourth reclose setting the longest time setting. Figure

3-5 illustrates a BE1-79A reclosing sequence and the relationship of each reclose setting to the breaker

openings.
The flow chart of Figure 3-6 is a simplified representation of reclosing sequence initiation and

progression.
If a reclosing sequence is interrupted by removing power supply voltage from terminal 5 or 6, this will

“freeze” the timing cycle at that point in the reclosing sequence. Freezing the timing sequence will result

in contact C10 and the RS contact returning to their de-energized state when the BE1-79A power supply

is de-energized. Once voltage is restored to the power supply, timing resumes from the point in the

reclosing sequence that the power supply was de-energized.
External restrictions such as “hot-bus, dead-line” should be connected between terminals 7 and 8 of the

BE1-79A to avoid de-energizing the power supply and “freezing” the timing sequence.