1-4
BE1-79A General Information
9310200990 Rev J
Qualified to IEEE C37.90.1-1989, Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems. The RS-232 Serial Communication Port is intended only for periodic use and
is not subject to the requirements of IEEE C37.90.1.
Surge Withstand Capability—Oscillatory and Fast Transient
Type tested using a 5 W, hand-held transceiver in the ranges of 144 and 440 MHz with the antenna
placed within 6 inches (152 millimeters) of the relay.
Radio Frequency Interference (RFI)
In standard tests, the relay has withstood 15 G in each of three mutually perpendicular planes without
structural damage or degradation of performance.
Shock
In standard tests, the relay has withstood 2 G in each of three mutually perpendicular planes, swept over
the range of 10 to 500 Hz for six sweeps, 15 minutes each sweep, without structural damage or
degradation of performance.
Vibration
Environment
Operating Temperature Range .. –40 to 70°C (–40 to 158°F)
Storage Temperature Range ..... –40 to 85°C (–40 to 185°F)
Humidity ..................................... Qualified to IEC 68-2-38, 1
st
Edition 1974, Basic Environmental Test
Procedures, Part 2: Test Z/AD: Composite Temperature Humidity Cyclic
Test
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.
Weight
BE1-79A-100, -101 .................... 5 lb (2.3 kg)
BE1-79A-200, -201 .................... 13 lb (5.9 kg)
Patent
Number 6,239,960
Maintenance
BE1-79A relays require no preventative maintenance. However, testing should be performed according to
scheduled practices. If the relay fails to function properly, contact the Technical Support Services
department of Basler Electric for a return authorization number before returning the relay for service.