BE1-79A Controls and Indicators
9310200990 Rev J
Style Configuration Switches
Three switches on the left side of the relay cradle are used to configure the BE1-79A for either ACR11A
or ACR11B operation. For simplicity, recloser styles ACR11B, ACR11C, ACR11D, ACR11E, and ACR11F
will be referred to as ACR11B throughout this manual. Figure 2-2 illustrates the location of the style
configuration switches. The BE1-79A is delivered with switches S1, S2, and S3 placed in the “A” position.
Figure 2-2. Style Configuration Switches
Instantaneous Reclose Jumper Switch and RS Contact Switch
Two switches on the right side of the relay cradle select either internal or external jumpering for an
instantaneous first reclosure and for selecting normally-closed or normally-open operation of the RS
contact. Switch S4 is used to select internal or external jumpering and switch S5 is used to select
normally-open or normally-closed operation of the RS contact. Figure 2-3 illustrates the location of
switches S4 and S5. The BE1-79A is delivered with switch S4 placed in the “EXT” position and switch S5
placed in the “NC” position.