Basler Electric BE1-25 User Manual
Page 64

Condition Switch
1
Up
2
Up
3
Up
4
Down
5
Up
Mode Switch†
1
Down
2
Down
Output∗ only when bus and line input voltages are less than 60 volts.
Condition Switch
1
Up
2
Up
3
Up
4
Up
5
Down
Mode Switch†
1
Down
2
Down
Output∗ only when bus and line input voltages are greater than 60 volts but less than 120 volts.
Condition Switch
1
Up
2
Down‡
3
Up
4
Up
5
Up
Mode Switch†
1
Down
2
Down
No output throughout voltage range. (Normal SYNC function still operates with the additional NOT
overvoltage constraint. Output occurs after 99 seconds time delay if the line and bus voltages are greater
than 60 Vac and less than the NOT overvoltage setting of 120 Vac.)
Condition Switch
1
Down
2
Up
3
Up
4
Up
5
Up
Mode Switch†
1
Down
2
Down
Notes for Table 5-2:
∗
Contact is SYNC output for output option E or F. Voltage Monitor output for output option G or H.
† Placing both bus and line NOT OV Mode Switches Down, does NOT imply that line and bus must
operate in the same mode. Any combination is permissible.
‡ The only valid use for the LB-LL Condition Switch No. 2 Down is when there is an independent output
relay for the Voltage Monitor output options G and H.
If the delta voltage option is present, it is factory set to 20 volts. (The timed SYNC output is inhibited if the
voltage difference between the line and the bus is greater than 20 volts.)
5-8
BE1-25 Testing
9170200990 Rev U