Line and Bus Voltage
Monitor Option
Range
Continuously adjustable over the range of 10 to 135 Vac.
Accuracy
The line and bus voltage setpoints do not vary more than 3% from
a reference measurement at 25°C, with nominal input frequency,
and with temperature and voltage inputs within specified operating
range. Setpoints do not vary more than 1% from a reading at 25°C
over the limited temperature range of +15 to +40°C.
Isolation
In accordance with IEC 255-5 and IEEE C37.90, one minute dielectric
(high potential) tests as follows:
All circuits to ground: 2,121 Vdc
Input to output circuits: 1,500 Vac or 2,121 Vdc
Surge Withstand Capability
Oscillatory
Fast Transient
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems.
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability
(SWC) Tests for Protective Relays and Relay Systems.
Radio Frequency
Interference (RFI)
Maintains proper operation when tested for interference in
accordance with IEEE C37.90.2-1987, Standard Withstand
Capability of Relay Systems to Radiated Electromagnetic
Interference from Transceivers.
UL Recognition
UL recognized per Standard 508, UL File No. E97033. Note:
Output contacts are not UL recognized for voltages greater than
250 V.
Shock
In standard tests, the relay has withstood 15 G in each of three
perpendicular planes without structural damage or degradation of
performance.
Vibration
In standard tests, the relay has withstood 2 G in each of three
mutually perpendicular axes swept over the range of 10 to 500
hertz for a total of six sweeps, 15 minutes each sweep, without
structural damage or degradation of performance.
Operating Temperature
–
40°C (–40°F) to 70°C (158°F).
Storage Temperature
–
65°C (–85°F) to 100°C (212°F).
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.
Weight
13.7 (6.2 kg) pounds maximum.
Case Size
S1 (Refer to Section 4 for case dimensions.)
9170200990 Rev U
BE1-25 General Information
1-11