Basler Electric BE1-25 User Manual
Page 30

Callout
Control or Indicator
Function
S
(Cont’d)
No. 2 (Live Line/Live Bus)
Up = OFF
Down = ON
When ON (Down), the Voltage Monitor Output relay is
actuated when a live line/live bus condition is recognized.
CAUTION
If relay has Output Option E or F:
Condition Switch No. 2 (LL-LB) must be Up
(OFF) when output option E or F is selected.
Otherwise, sync outputs will occur under live
line/live bus conditions without benefit of the
Sync-Check function. No switch or contact
should be connected to the LL-LB input
terminal in this case.
CAUTION
If relay has Output Option G or H:
Condition Switch No. 2 (LL-LB) may be Down
(ON) only when output option G or H has been
selected and the Voltage Monitor Output
contacts do not by-pass the Sync-Check
contact. Use of the external LL-LB switch (if
installed) is similarly limited.
No. 3 (Dead Line/Live
Bus)
Up = OFF
If relay has Output Option E or F:
The ON (Down) position causes immediate closure of the
Sync Output contact, if a dead line/live bus condition is
detected with the breaker open.
If relay has Output Option G or H:
The ON (Down) position causes immediate actuation of
the Voltage Monitor relay, if a dead line/live bus condition
is detected with the breaker open.
2-6
BE1-25 Controls and Indicators
9170200990 Rev U