beautypg.com

Ip module, Quick start guide – Auto-Zone Control Systems IP Module Kit Installation Guide for the IP Module Kit Used with CommLink IV & 5 (Version 01N) User Manual

Page 4

background image

IP MODULE

4

Technical Guide

Quick Start Guide

Quick Start Guide

NOTE:

Please note, the R(+) and T(-) terminals on the

communications terminal block are reversed from all
previous versions of the CommLink.

WARNING:

If you are replacing an earlier version of the

CommLink with a CommLink 5, be aware that the polarity

of the terminal block is reversed on the CommLink 5

from all previous models. You must always confi rm that

the polarity is correct when wiring 24 VAC power to the

CommLink power terminal block or serious damage to the

product will result.

Follow the steps below to get your IP Module up and running
in no time.

Step 1:

Open your CommLink and snap in your IP

Module.

See Figure 1, page 5 for CommLink IV

directions

and

Figure 2, page 6 for CommLink 5

directions.

Step 2:

Set your CommLink’s communication switch to

Multiple

or

Single.

See Figure 3, page 7 for

CommLink

IV

directions

and

Figure 4, page 8

for

CommLink

5

directions.

Step 3:

Set your CommLink 5’s Baud Rate switch to High

or

Low.

See

Figure 5, page 9

.

Step 4:

Wire your CommLink to the appropriate controller

on your system and plug the CommLink into a
power

supply.

See

Figure 6, page 10 for

CommLink

IV

directions

and

Figure 7, page 11

for CommLink 5 directions.

Step 5:

Connect your CommLink to your PC via

Ethernet

cable.

See

Figures 8 & 9, page 12.

Step 6:

Change your PC’s IP address. See Figure 13,

page 13.

Step 7:

Change the IP address of your CommLink. See

page 14 for instructions.

Step 8:

Set the baud rate for your CommLink in

the

Confi guration Settings. See page 14 for

instructions.

IMPORTANT NOTES:

‮ Follow the included CommLink connection and
wiring instructions sheet (See Figure 6, page 10 or
Figure 7, page 11) to connect and confi gure the
CommLink for an Ethernet connection.

‮ Make sure you follow the appropriate directions for
your

Windows

®

version.

‮ Familiarize yourself with all system components and
review all documentation. Pay special attention to
“Cautions,” “Notes,” and “Warnings” since these may
keep you from experiencing unnecessary problems.

‮ If you encounter any problems, please refer to the
Troubleshooting section of this guide fi rst. If you
can’t resolve the problem, please call WattMaster
Technical Support at our toll free number—
1-866-918-1100.