Appendix c - system manager ts alarm polling, Setting up alarm polling for the system manager ts – Auto-Zone Control Systems Prism 2 Graphical Interface Technical Guide (Version 01J) User Manual
Page 42

APPENDIX C - SYSTEM MANAGER TS ALARM POLLING
Prism 2 Technical Guide
42
Setting Up Alarm Polling for the System Manager TS
Revised 8/29/11
Setting Up Alarm Polling for the
System Manager TS
NOTE:
This section applies to System Manager Touch Screen
Alarm Polling only. For Prism 2 Alarm Polling, see Section 9.
Using Prism 2 to set up Alarm Polling for the System Manager
TS, you must have a CommLink and MiniLink Polling Device
installed on your system. The following procedure must be done
for the MiniLink Polling Device on each loop.
In the Loop Selection Window of the Prism
2 Main Screen, select the loop where your
MiniLink Polling Device is located. Then,
in the Unit Selection Window scroll down to
Address 60 - MiniLink PD and click once
on your selection.
Click the
option at the top far right of the Polling
Device Setpoints Window. The Alarm / Override Polling Window
will appear.
In the Alarm / Override Polling Window, click the box to the left of
each controller to choose alarm polling and push-button overrides
for that controller. A check mark in the box designates alarm
polling/push-button override.
The Polling Device Window will appear.
Click
at the top of the screen. The Polling Device
Setpoints Window will appear.