beautypg.com

Section 2 isolated analog programmer operation, 1 sw1 switch, Isolated analog programmer operation – AMETEK DCS-E 1kW Series Programming Manual User Manual

Page 13

background image

SECTION 2

ISOLATED ANALOG

PROGRAMMER OPERATION

2.1 SW1 Switch

The SW1 SETUP switch is accessible from the rear panel of the unit. It provides user selection
of the programming/monitoring ranges and shutdown logic signal level. Setting a switch to the 1
or 0 position changes a range. The factory default settings are shown below.

Refer to Figure 2–1 for a rear panel view of the DLM-E 3kW and 4kW models.
Refer to Figure 2–2 for a rear panel view of the DCS-E 1kW models.

Switch

Position

Function

OFF (0) Position

ON (1) Position

1

Voltage Programming

Range Select

0-10 VDC

* 0-5 VDC, 4-20mA

2

Current Programming

Range Select

0-10 VDC

* 0-5 VDC, 4-20mA

3

OVP Programming

Range Select

0-10 VDC

* 0-5 VDC

4

Output Voltage Monitor

Range Select

* 0-5 VDC

0-10 VDC

5

Output Current Monitor

Range Select

* 0-5 VDC

0-10 VDC

6

Remote ON-OFF Level

Select

Active Low Signal

* Active High Signal

* Indicates default settings

Table 2–1. SW1 SETUP Switch

M51A Option

2-1