4
Dimming Channel 2 functions (factory default in brackets):
4.1
Light level
Maintained illuminance level (adjustable between 1 and 999). At 999 the
output will be always be at maximum.
4.2
Presence detection
Auto switch on with detection, auto off after movement ceases and
(default)
time delay ends.
4.3
Absence detection
Manual switch on, auto off after movement ceases and time delay ends.
4.4 Switch level on (9)
Lux level setting to prevent the luminaires being switched on if the
ambient light level is sufficient (adjustable between 1 and 9). The
luminaires will always be switched on at level 9. For a higher resolution of
‗switch level on‘ a scale of 101-199 is available in the ‗Special menu‘.
4.5 Switch level off (9)
Lux level setting to switch the luminaires off during occupancy if the
ambient light level goes above the setting (adjustable between 1 and 9).
Level 9 will always keep the lights on. This setting can be used for
―window row switching‖. For a higher resolution of ‗switch level on‘ a scale
of 101-199 is available in the ‗Special menu‘.
4.6
DSI (default)
Selects DSI dimming
4.7
DALI
Selects DALI dimming
4.8
Memorise (N)
If this is set to Yes, the last manual lux level set will be memorised and
used as the new switch on level.
4.9
On value (99)
Dimming output level when switched on (0-99).
4.10 Off value (0)
Dimming output level when switched off (0-99). If a non-zero off value is
set, then the output will toggle between this value and completely off
depending on the switch level on and off values. For example, if it is light
outside, the fittings will be off if there is no occupancy. If it is dark outside,
they will adopt the preset off value. This feature is only enabled if ‗Min
value‘ is set to 99.
4.11 Fade value (10)
After occupancy ceases, this dimming output level is loaded for the fade
time (adjustable between 0 and 99).
4.12 Fade mins (0)
This is the time period (adjustable between 0 and 99 minutes) that the
luminaire will be held at the fade value before turning off. A value of 0
disables the fade function.
4.13 Max value (99)
Maximum dimming output level (adjustable between 0 and 99).
4.14 Min value (1)
Minimum dimming output level (adjustable between 0 and 99).
4.15 Speed on (40)
Determines the dimming response speed after the setup time has
finished. Measured in 0.1 sec intervals.
4.16 Speed set (5)
Determines the dimming response speed during the set up time.
Measured in 0.1 sec intervals. If set to 0 will disable dimming for ―Set
seconds‖ below, used if fittings are required to warm up before dimming.
4.17 Set seconds (120)
Determines how long the dimming response set-up period lasts on power-
up or on setting change (adjustable between 1 and 999 seconds). This
enables the desired lux level to be achieved rapidly when the lights come
on, or during setup.
4.18 Burn-in (0)
Determines how long the output will be at 100% so that lamps ‗burn-
in‘ (adjustable between 1 and 999 hours). The ‘burn-in‘ time is not affected
by power supply interruptions. To disable burn-in set to 0.
4.18 DALI on (off)
Provides a permanent voltage to DALI ballasts when DALI has not been
implemented correctly in the ballast. Maximum number of ballasts is 10
unless the relay is disabled then it is 20. This is a Special menu option.
5
User Menu
DD-LCDHS user menu or UHS handset functions:
5.1
Lux up
Increase light level. Reverts when occupancy cycle complete.
5.2
Lux down
Decrease light level. Reverts when occupancy cycle complete.
5.3
Scene up
Steps up between 6 pre-defined scenes.
5.4
Scene down
Steps down between 6 pre-defined scenes.
5.5
Scene#
Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%;
3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%)
5.6
Override on
Permanently overrides the luminaire output on.
5.7
Override off
Permanently overrides the luminaire output off.
5.8
Cancel
Cancels the on or off override, returning the detector to normal operation.
5.9
Set
If sent before using lux up or lux down, it will set the light level as in 4.1