11. Detection Patterns

Ideal for large office or classroom

Ideal for corridor or aisle applications

Ideal for open plan areas and offices

LOAD DOES NOT COME ON

Check to see if the live supply to the circuit is
good. Strap across the L and LIVE OUT terminal
to turn the load on.

If the supply and wiring are good, check the LUX
level setting. Increase the LUX level setting to
allow the controller to turn on at higher ambient
natural light level.


LIGHTS DO NOT GO OFF

Ensure that the area is left unoccupied for a
greater time period than the time out period set
using the switch.

Make sure that the sensor is not adjacent to
vibrating surfaces or objects (e.g. ventilation
equipment).

The unit may pick up movement through thin
partitions or walls. Reduce the sensitivity by
turning the adjuster anticlockwise.

12. Fault Finding