LOAD
Channel 1 (switching):
10A of lighting and or ventilation including incandescent, fluorescent, compact fluorescent, low voltage
(switch primary of transformer).
Channel 2 (dimming):
Maximum number of DSI or DALI ballasts is 10 unless the relay is disabled then it is 20.
SUPPLY VOLTAGE

220-240 Volts AC 50 Hz

TIME OUT PERIOD

Adjustable 10 seconds to 99 minutes

LIGHT LEVEL

Light to dark

TERMINAL CAPACITY 2.5mm

2

MATERIAL

Flame retardant ABS

TYPE

Class 2

TEMPERATURE

-10°C to 35°C

SAFETY

The microwave radiation emitted by these units is exteremely low power.

At a distance of > 50mm the power density is <6% of the ANSI IEEE C95.1 –1991
recommended microwave power density.
At a distance of 5mm from the unit it is <84% of recommended power density.

CONFORMITY

EMC-89/336/EEC
LVD-73/23/EEC

14. Part Numbers

13. Specification

MWS3A-DD

Microwave Direct Dim presence detector

MWS3A-DD/ABS

Microwave Direct Dim absence detector

MWS3A-DD/PRG

Microwave detector pre-commissioned (contact sales department)

MWS3A-DBB

Surface mounting box

DD-LCDHS

IR remote control programming handset with LCD screen

UHS

IR remote control user handset with lux setting functionality

UHS3

IR remote control user handset with on/off override only

Ref #WD288 Issue 3

C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:

+ 44 (0) 333 900 0671

Fax:

+ 44 (0) 333 900 0674

www.cpelectronics.co.uk
[email protected]

IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE wiring regulations.

Due to our policy of continual product improvement CP Electronics reserves the right
to alter the specification of this product without prior notice.