9. Programming

All the following functions can be programmed using the remote control DD-LCDHS handset:

1. Detector Parameters (factory default in brackets):

1.1 Time adjustment

10 seconds to 99 minutes time delay (select 0 for 10 second

delay – use for commissioning only).

1.2 Sensitivity On (9)

Sensitivity level when the detector is already operational

adjustable between 1 (min.) and 9 (max.)

1.3 Sensitivity Off (9)

Sensitivity level for switching the detector on – adjustable

between 1 (min.) and 9 (max.).

1.4 Power Up On (Y)

Select No for a 30 second delay on start up. If Yes is selected,

there will be no delay on start up and the detector will always

power up detecting.

1.5 Walk Test (N)

An LED behind the detector lens will flash to show movement

has been detected (use for commissioning).

1.6 Disable Detector (N)

Disables detection, leaving the relay output permanently off

with the dimming output operational. This mode is used when

the unit is for maintained illuminance only.

1.7 Factory Default

Restores factory default settings.

2. Modes (factory default in brackets):

2.1 Channel Modes

2.1.1 Switch only

Usually used for absence detection - in this mode the dimming

channel is not used.

2.1.2 Switch and dim together (default) The detector will switch and dim the lighting together.
2.1.3 Switch and dim separate

Provides 2 channel operation – Channel 1 is switched via the

relay output, and Channel 2 is dimmed / switched via the

dimming output.

2.2 Switch Modes

2.2.1 2 position switch together (default) A single centre biased retractive switch will be used to

control both channels together.

2.2.2 2 position switch separate

A single centre biased retractive switch will be used to

control only the dimming channel.

2.2.3 1 position switch together

A single position retractive switch controls both channels

together.

2.2.4 1 position switch separate

Two single position retractive switches, controlling the

channels separately.

3. Switching Channel 1 functions (factory default in brackets):

3.1 Presence detection

Auto switch on with detection, auto off after movement ceases

(MWS3A-DD default) and time delay ends.

3.2 Absence detection

Manual switch on, auto off after movement ceases and time

(MWS3A-DD/ABS default) delay ends.

3.3 Switch level on (9)

Lux level setting to prevent the luminaires being switched on if

the ambient light level is sufficient (adjustable between 1

and 9). The luminaires will always be switched on at level 9.

For a higher resolution of ‗switch level on‘ a scale of 101-199

is available in the ‗Special menu‘.

3.4 Switch level off (9)

Lux level setting to switch the luminaires off during occupancy

if the ambient light level goes above the setting (adjustable

between 1 and 9). Level 9 will always keep the lights on. This

setting can be used for ―window row switching‖.

For a higher resolution of ‗switch level off‘ a scale of 101-199

is available in the ‗Special menu‘.