Basic maintenance protocol, Maintenance, Safety regulations – CIRCUTOR OPTIM HYB Series User Manual
Page 27: Maintenance with the capacitor bank disconnected

5.- MAINTENANCE
5.1.- SAFETY REGULATIONS
Take the safety regulations listed in section of this manual into account before
operating the units
“3.1.- PRELIMINARY RECOMMENDATIONS”
The National Electric Code of the country where the capacitor bank is installed or
operated should be strictly followed.
5.2.- MAINTENANCE WITH THE CAPACITOR BANK DISCONNECTED
5.2.1. BASIC MAINTENANCE PROTOCOL
Monthly:
Visually inspect the capacitors.
Check the protection circuit breakers.
Control the ambient temperature (average of 30 ºC In accordance with IEC 60831 ).
Control the service voltage (especially during moments of low load, it must not exceed
the nominal +10%).
Bi-annually:
Keep the capacitor terminals clean.
Check that the thyristors are not short-circuited.
To do so, check that if you cut the power supply of the regulator there is no current in any
of the capacitor phases.
Check that the capacitor current is not lower than 75% nor greater than 120% of the
nominal value by phase and that there is no phase unbalance greater than 15%.
Annually:
Check the capacity of the capacitors at the different steps.
An indirect verification can be performed by checking that the consumption matches the
value indicated in
, with a maximum deviation of ± 10%.
Check the tightening torque of all terminal connections on the different power ele-
ments.
Inspect the fuses.
-
Power Circuit: Check the continuity and temperature of the unipolar and three-pole
circuit breakers.
-
Control Circuit: Check the continuity and temperature of the quadrupole circuit break-
er.
27
Instruction Manual
OPTIM HYB Series