beautypg.com

CIRCUTOR OPTIM HYB Series User Manual

Page 10

background image

The available combinations for standard models are selected through internal mini-dips.

The programming is done in-factory and should not be modified, except by

CIRCUTOR personnel or by those properly trained in its use.

Note: If you need to find out the configuration of the mini-dips for each combination, please

contact

CIRCUTOR technical assistance.

The available staging combinations as of the date of publication of this manual are exclusively

those indicated in

Table 2

:

Table 2:Available stage combinations.

Model

Composition

OPTIM HYB1-90-440

(3 x 2 x 5) kvar / 230 V + (3 x 15) kvar / 400 V / 50 Hz

OPTIM HYB1-110-440

(3 x 2 x 5) kvar / 230 V + (4 x 15) kvar / 400 V / 50 Hz

OPTIM HYB2-165-440

(3 x 3 x 5) kvar / 230 V + (3 x 30) kvar / 400 V / 50 Hz

OPTIM HYB2-200-440

(3 x 3 x 5) kvar / 230 V + (4 x 30) kvar / 400 V / 50 Hz

OPTIM HYB2-270-440

(3 x 3 x 5) kvar / 230 V + (6 x 30) kvar / 400 V / 50 Hz

OPTIM HYB2-325-440

(3 x 3 x 10) kvar / 230 V + (3 x 60) kvar / 400 V / 50 Hz

OPTIM HYB3-400-440

(3 x 3 x 10) kvar / 230 V + (4 x 60) kvar / 400 V / 50 Hz

OPTIM HYB3-470-440

(3 x 3 x 10) kvar / 230 V + (5 x 60) kvar / 400 V / 50 Hz

OPTIM HYB3-540-440

(3 x 3 x 10) kvar / 230 V + (6 x 60) kvar / 400 V / 50 Hz

Digital input for external temperature relay signal (

Figure 4

) installed at the top of the heatsink

to dissipate the semiconductors. ( Normally in closed position )

In the event of an alarm, the connected steps would disconnect until the thermal relay returns

to its NC position and the condition triggering the alarm disappears.

The alarm situation is indicated by a combination of lit LEDs on the front panel of the

Computer

HYB (See

Figure 5

).

Lack of compensation alarm, installed in the

Computer HYB.

The alarm goes off when the non-compensated three-phase power is greater than 30% of the

total three-phase power available in the capacitor bank, or in other words, is greater than 30%

of its nominal power of 400 V~.

The alarm situation is indicated by the

cos φ LED being lit on the front panel of the Computer

HYB. (See

Figure 5

).

2.1.1.1. Computer HYB Regulator Connections.

Note : See the general connection diagram in “7.- OPTIM HYP type diagram”

The regulator comes fully connected, expect in the case of units that do not have the CVM-MI-

NI-RS485 analyzer.

In this case, you must connect the CVM-MINI-RS485 communications output to the

ASB COM2

terminal of the

Computer HYB, using a shielded communication cable with at least 3 wires and

with a section of at least 0.25 mm

2

.

10

OPTIM HYB Series

Instruction Manual