Technical data – CIRCUTOR DHB Series User Manual
Page 44

44
8. TECHNICAL DATA
Measuring ranges
Table 13
Kind of input
Indication range
Class
Pt100
-205...855
°C (-200...850°C)
0.1
Pt500
Pt1000
400
W
0...410
W (0...400 W)
4000
W
0...4010
W (0...4000 W)
Thermocouple of J type
-200...1200
°C (-100...1200 °C)
Thermocouple of K type
-200...1370
°C (-100...1370 °C)
Thermocouple of N type
-200...1300
°C (-100...1300 °C)
Thermocouple of E type
-200...1000
°C (-100...1000 °C)
Thermocouple of R type
-50...1768
°C (-50...1760 °C)
Thermocouple of S type
-50...1768
°C (-50...1760 °C)
Voltage input 0...10 V
-13...13 V (-10...10 V)
Current imput
-24...24 mA (-20...20 mA)
Voltage input 60 mV
-10...63 mV (0...60 mV)
Current time
00.00...23.59
0.5 sec/24 h
Additional error:
- of automatic thermocouple cold junction temperature compensation:
1
°C
- of automatic wire resistance compensation for thermoresistors:
0,5
°C
- of automatic wire resistance compensation for resistance measurement:
0,2 W
- of temperature changes:
for analog outputs 50 % of the class / 10 K
for analog inputs 100 % of the class / 10 K
Inputs parameters:
- resistance of the supply input [V]:
> 1 M
W
- resistance of the current input [mA]:
12 ±1
W%
- current flowing through the resistance thermometer
270 ± 10 uA
- resistance of wires connecting the resistance thermometer with transmitter: <10
W