beautypg.com

Cnt1 – CIRCUTOR DHB Series User Manual

Page 18

background image

18

Table 2

Ind

Parameter

symbol

Description

Range of changes

IndCp

Number of points of the individual
characteristic. For a value lower than 2,
the individual characteristic is switched
off. The number of segments is the
number of points decreased of one.
The individual characteristic is not taken
into consideration in the CountH and
HoUr modes.

1...21

Hn

The point value for which we will expect
Yn (n-point number)

-19999...99999

Yn

Expected value for Xn.

-19999...99999

cd. Table 1

Con

Choice of the measured value
compensation. Concerns only the
work in the mode of temperature
or resistance measurement. The
wire linking the meter with the
sensor defines the resistance
for RTD sensors, however for
thermocouples, the compensa-
tion is defined by the cold junc-
tion temperature. The choice of a
value beyond the range causes
the switching of the automatic
compensation on.

-19999...99999

Introduction of values:
0..20

W - causes the switching

of the manual compensation on
for the resistance or tempera-
ture measurement by means of
RTD (resistance thermometers).
0...60

o

C – causes the switching

of the manual compensation on
for thermocouples.

Cnt1

The measurement time is
expressed in seconds. The result
on the display presents the mean
value counted in the Cnt1 period.
This parameter is not taken into
consideration during the
measurement in counter modes.

1...3600