CIRCUTOR DHB Series User Manual
Page 36

36
Type of analog output
4030
tYPa
w/r
0...2
Value
0
voltage input 0...10 V
1
current input 0...20 mA
2
current input 4...20 mA
Description
Baud rate
4031
bAud
w/r
0...5
Value
0
4800 bit/s
1
9600 bit/s
2
19200 bit/s
Description
3
38400 bit/s
4
57600 bit/s
5
115200 bit/s
Meter address. The write of the value 0 causes the
interface switching off
4033
Addr
w/r
0...247
Transmission mode
4032
prot
w/r
0...3
Update transmission parameters. Causes the
application of introduced RS-485 interface settings.
4034
sAvE
w/r
0...1
value
0
RTU 8N2
1
RTU 8E1
2
RTU 8O1
3
RTU 8N1
Description
Write of standard parameters
4035
SEt
w/r
0...1
Value
0 without changes
1 set standard parameters
Description
Password for parameters
4036
SEc
w/r
0...6000
Value
0
without password
... Entry in parameters preceded by a
request about the password
Description
Current time
4037
hour
w/r
0...2359
This parameter occurs in the ggmm format, where:
gg - means hours,
mm – means minutes.
The introduction of a wrong hour will cause the
setting of 23, however the introduction of wrong
minutes will generate the setting of the value 59.