beautypg.com

Current energy variables – CIRCUTOR QNA500 series User Manual

Page 86

background image

POWER QUALITY ANALYZER QNA500 8IO

QNA500 8IO Instruction manual

86 / 111

MODBUS VARIABLES

VARIABLE

SYMBOL

INSTANTANEOU

S

MAXIMUM

MINIMUM

UNITS

THD

THD U1

THDU1

50 – 51

1ª0 – 1ª3

3ª0 – 3ª3

%x10

THD U 2

THDU2

52 – 53

1ª4 – 1ª7

3ª4 – 3ª7

%x10

THD U 3

THDU3

54 – 55

1ª8 – 1AB

3ª8 – 3AB

%x10

THD UN

THDUN

56 – 57

1AC – 1AF

3AC – 3AF

%x10

THD I 1

THDI1

58 – 59

1B0 – 1B3

3B0 – 3B3

%x10

THD I 2

THDI2

5A – 5B

1B4 – 1B7

3B4 – 3B7

%x10

THD I 3

THDI3

5C – 5D

1B8 – 1BB

3B8 – 3BB

%x10

THD IN

THDIN

5E – 5F

1BC – 1BF

3BC – 3BF

%x10

Unbalance

U Unbalance

Kd U

60 – 61

1C0 – 1C3

3C0 – 3C3

%x10

U Asymmetry

Ka U

62 – 63

1C4 – 1C7

3C4 – 3C7

%x10

I Unbalance

Kd I

64 – 65

1C8 – 1CB

3C8 – 3CB

%x10

I Asymmetry

Ka I

66 – 67

1CC – 1CF

3CC – 3CF

%x10

FLICKER

PST V1 Statistical Flicker

PST_V1

68 – 69

x10

PST V2 Statistical Flicker

PST_V2

6A – 6B

x10

PST V3 Statistical Flicker

PST_V3

6C – 6D

x10

EARTH LEAKAGE
CURRENT

Id

Id

6E – 6F

1D0 – 1D3

3D0 – 3D3


Current energy variables

MODBUS VARIABLES

VARIABLE

SYMBOL

Wh

mWh

Active energy

kWh III

500 - 501

502 - 503

Inductive reactive energy

kvarhL III

504 - 505

506 - 507

Capacitive reactive energy

kvarhC III

508 - 509

50A - 50B

Active energy generated

kWhIII (-)

50C - 50D

50E - 50F

Inductive energy generated

kvarLhIII (-)

510 - 511

512 - 513

Capacitive energy generated

kvarChIII (-)

514 - 515

516 - 517