POWER QUALITY ANALYZER QNA500 8IO
QNA500 8IO Instruction manual
81 / 111
with peripheral number 23 to generate pulses proportional to the energy measured by a
QNA500 module with peripheral number 22 with the use of a WEB server).
First, create the energy object in QNA500
• Open the Configure Objects menu of the QNA500
• Activate Digital Object 1
• Active Checkbox: Enabled
• Type: Energy + (
three-phase active energy
)
• Description: Active energy (
for example
)
• Send to: 23 (
peripheral number of the M-8IO
)
• Active: Enabled
• Press the Update button
Return to the WEB server of the M-8IO module.
• Select the new energy object from the list (
8 available
): 1
• Peripheral: 22
• Energy object: 1 (
previously configured in the QNA500 8IO
)
• Description: Active energy (
for example
)
• Quantity: 1 (
this would generate 1 pulse every 1 W/h
)
• Units: W
• T
ON
: 10 (
this time is multiplied x10ms, i.e., the minimum possible
)
• T
OFF
: 10 (
this time is multiplied x10ms, i.e., the minimum possible
)
• Hardware Output: 3 (
pulse output being activated
)
• Active Checkbox: Enabled