Alarm setup (digital objects) – CIRCUTOR QNA500 series User Manual
Page 35

POWER QUALITY ANALYZER QNA500 8IO
QNA500 8IO Instruction manual
35 / 111
QNA500 analyzer will record all variables selected every X minutes once the variables have been
selected and the new configuration has been sent, in accordance with the programmed standard
recording time period.
These records are saved in various files, depending on the type of data. Refer to the file section for
more information related to the location of these information records.
8.11.- ALARM SETUP (Digital objects)
QNA500 power quality analyzer can configure a list of alarms (up to 16 alarms) for an improved and
more accurate supervision of the electrical installation and its status.
These alarms can be simply recorded in the memory or used to create actions in other MULTIFIT
modules, such as, for example, the activation of the relay of a M-8IO module.
There are 2 different types of alarms (or digital objects), as described:
• ALARM OBJECTS: can enable any alarm condition associated to an electrical variable
measured by the QNA500 module.
• ENERGY OBJECTS: these are necessary when associating a pulse output of a M-8IO module.
The most common application is where the pulse outputs can produce pulses proportional to
the energy (A+, A-, Q1, Q2, Q3 or Q4) measured by the QNA500. To do so, first activate an
energy object and activate the pulse output on the M-8IO module. This configuration is
explained in the corresponding chapter of this module.
These alarms (or digital objects) can be associated with the following variables:
Variable description
Variable code
L1 Voltage
1
L2 Voltage
2
L3 Voltage
3
N-G Voltage
4
Voltage III
5
L1-L2 Voltage
10
L2-L3 Voltage
11
L3-L1 Voltage
12
L1 Current
20
L2 Current
21
L3 Current
22
Neutral Current
23
Current III
24
L1 Active Power
30
L2 Active Power
31
L3 Active Power
32
III Active power
33
L1 Inductive Power
35
L2 Inductive Power
36
L3 Inductive Power
37
III Inductive Power
38
L1 Capacitive Power
40
L2 Capacitive Power
41
L3 Capacitive Power
42
III Capacitive Power
43
L1 Apparent Power
45
L2 Apparent Power
46
L3 Apparent Power
47
III Apparent power
48
Angle V1-V2
60
Angle V2-V3
61