Pilz PSSnet SHL 8T MRP User Manual
Page 48

Ring/Network coupling
48
3.2 Preparing a Ring/Network cou-
pling
PSSnet SHL - Redundancy Configuration
Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern
Note: Configure the coupling port and the redundancy ring ports on different
ports.
Select two-Switch redundant coupling
with control line
(see fig.
24)
.
Figure 24: Two-Switch coupling with control line
1: Coupling port
2: Partner coupling port
3: Control line
The following settings apply to the Switch displayed in blue in the
selected graphic.
Select the coupling port
(see fig.
23)
,
(see table
9)
.
With “Coupling port” you specify at which port you are connecting
the network segments.
If the STANDBY DIP switch is ON, connect the main line to the
coupling port.
Select the control port
(see fig.
23)
,
(see table
9)
.
With “Control port” you specify at which port you are connecting the
control line.
Activate the function in the “Operation” frame
(see fig.
16)
.
You now connect the redundant line and the control line.
The displays in the “Select port” frame mean
(see fig.
23)
:
– “Port mode”: The port is either active or in stand-by mode.
– “Port state”: The port is either connected or not connected.
– “IP Address”: The IP address of the partner, if the partner is already
operating in the network.
I O
STAND-BY
1
2
3