Overview of redundancy, Procedure, 1 overview of redundancy procedure – Pilz PSSnet SHL 8T MRP User Manual
Page 10

Introduction
10
1.1 Overview of
Redundancy
Procedure
PSSnet SHL - Redundancy Configuration
Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern
1.1 Overview of
Redundancy Procedure
Redundancy
procedure
Network topology
Switching time
RSTP
Random structure
typically < 1 s (STP < 30 s), up to < 30 s - depends
heavily on the number of devices
Note: Up to 79 devices possible, depending on topology and configuration. If
the default values are being used, up to 39 devices are possible, depending on
the topology
(see page
53)
.
HIPER-Ring
Ring
typically 80 ms, up to < 500 ms - practically indepen-
dently of the number of devices
MRP-Ring
Ring
typically 80 ms, up to < 500 ms - practically indepen-
dently of the number of devices
Note: In combination with RSTP in MRP compatibility mode, up to 39 devices
are possible, depending on the configuration. If the default values for RSTP are
being used, up to 19 devices are possible
(see page
53)
.
Redundant
coupling
Coupling of network
segment/rings via a
main line and a
redundant line
typically 150 ms, up to < 500ms
Table 1: Comparison of the redundancy procedures